Paper II — Q5
(a) Determine the inductance of a single-phase transmission line consisting of three conductors of 2 cm radii in the 'go'…
Determine the inductance of a single-phase transmission line consisting of three conductors of 2 cm radii in the 'go' conductor and two conductors of 4 cm radii in the 'return' conductor as shown in the figure below : [Figure: composite conductor A with strands a, b, c of 2 cm radius in a vertical column, 4 m apart (a to c 8 m), and composite conductor B with strands a′ and b′ of 4 cm radius, 4 m apart, in a parallel column 6 m away, a′ level with a and b′ level with b] 10 marks
The schematic diagram of a radial transmission system is shown in the figure below. The ratings and reactances of various components are shown therein. A load of 60 MW at 0.9 power factor lagging is tapped from 66 kV substation which is to be maintained at 60 kV. Calculate the terminal voltage of the synchronous generator : [Figure: generator at bus V1, 11/220 kV transformer 100 MVA X = 12%, line j100 Ω, 220/66 kV transformer 100 MVA X = 10%, bus V2 at 60 kV supplying 60 MW at 0.9 pf lagging] 10 marks
Explain how arc is initiated and sustained in a circuit breaker when the circuit breaker contact separates. Also, derive an expression for the restriking voltage in terms of system voltage, inductance and capacitance, across the circuit breaker contacts. (Assume that the neutral of the system is solidly grounded) 10 marks
Show that, with a non-uniform quantizer, the mean square value of the quantization error is approximately equal to 1/12 ∑ Δi² pi, where Δi is the ith step size and pi is the probability that the input signal amplitude lies within the ith interval. Assume that the step size Δi is small compared with the excursion of the input signal. 10 marks
Prove that all vectors in the same coset have the same syndrome that is unique to that coset in the standard array for any linear block code. 10 marks
हिंदी में प्रश्न पढ़ें
नीचे चित्र में एक एकल-कला संचरण लाइन दर्शाई गई है, जिसमें 'गो' संयुक्त चालक में 2 cm त्रिज्या के तीन चालक एवं 'रिटर्न' संयुक्त चालक में 4 cm त्रिज्या के दो चालक हैं। इस एकल-कला संचरण लाइन का प्रेरकत्व ज्ञात कीजिए : [figure] (10 अंक)
नीचे चित्र में एक विद्युत (रेडियल) संचरण नियाम का योजनाबद्ध आरेख दर्शाया गया है। विभिन्न घटकों के अनुमतक एवं प्रतिघात भी चित्र में प्रदर्शित किए गए हैं। 0.9 परचत शक्ति गुणक पर 60 MW का एक भार 66 kV के उपकेन्द्र (सब-स्टेशन), जिसे 60 kV पर बनाए रखा जाना है, से निष्कासित किया जाता है। तुल्यकालिक जनित्र की अन्त्य वोल्टता ज्ञात कीजिए : [figure] (10 अंक)
जब एक परिपथ विद्योजक का संपर्क विलग होता है, तो परिपथ विद्योजक में आर्क कैसे प्रारम्भ होता एवं निरंतर रहता है? समझाइए। साथ ही नियाम वोल्टता, परिपथ विद्योजक के संपर्क के आर-पार प्रेरकत्व एवं संधारित्र के सापेक्ष पुनः-प्रवर्तित वोल्टता के लिए एक व्यंजक निकालिए। (मान लीजिए कि नियाम का न्यूट्रल दृढ़ता से भू-संपर्कित है) (10 अंक)
प्रदर्शित कीजिए कि एक असमान प्रतिचयक (क्वांटक) के साथ क्वांटिकरण त्रुटि के वर्ग माध्य का मान लगभग 1/12 ∑ Δi² pi के बराबर होगा, जहाँ Δi, iवाँ पद आकार है तथा pi, निबिड संकेत (सिग्नल) के आयाम के iवाँ अंतराल में पाए जाने की प्रायिकता है। मान लीजिए कि पद आकार Δi, निबिड संकेत के प्रभाव (एक्सकर्सन) की तुलना में न्यून है। (10 अंक)
सिद्ध कीजिए कि किसी रेखिक खण्ड कूट के मानक आन्यूह के किसी सहसमुच्चय के सभी सदिशों का सिंड्रोम समान होता है एवं यह सिंड्रोम उस सहसमुच्चय के लिए अनन्य होता है। (10 अंक)
The figure this question refers to, in words
The question paper is a scan and the diagram did not survive as text. This is the figure as read from the original page — every component, value and label — so the question can be worked from the text below.
(a) Composite conductors: A = a, b, c (r = 2 cm) vertically 4 m apart, B = a′, b′ (r = 4 cm) 4 m apart, columns 6 m apart. (b) Radial system: G, 11/220 kV 100 MVA X 12%, line j100 Ω, 220/66 kV 100 MVA X 10%, load 60 MW 0.9 pf lag at V2 = 60 kV.
Model answer
Drafted with AI by UPSC Answer Check against this question's marking rubric, to the expected length. UPSC does not publish answers for Mains — this is one way to score well, not an official key. How we build rubrics and answers.
(a) Inductance of the composite-conductor line
Composite conductor A (the 'go') is the three strands a, b, c, radius 2 cm, one above the other 4 m apart; composite conductor B (the 'return') is the two strands a', b', radius 4 cm, 4 m apart, in a second column 6 m away, with a' level with a and b' level with b. The inductance of each composite conductor is L = 2 × 10⁻⁷ ln(Dm/Ds) H/m, with Dm the mutual GMD between the two groups and Ds the self GMD of the group.
Mutual GMD. The six distances from a strand of A to a strand of B are: a–a' = 6, a–b' = √(6² + 4²) = 7.211, b–a' = 7.211, b–b' = 6, c–a' = √(6² + 8²) = 10, c–b' = 7.211 m.
Dm = (6 × 7.211 × 7.211 × 6 × 10 × 7.211)^(1/6) = (360 × 7.211³)^(1/6) = (1.350 × 10⁵)^(1/6) = 7.16 m.
Self GMD of A. With r' = 0.7788 × 0.02 = 0.01558 m, the nine distances are r', 4, 8 (from a), 4, r', 4 (from b) and 8, 4, r' (from c):
DsA = (r'³ × 4 × 8 × 4 × 4 × 8 × 4)^(1/9) = (0.01558³ × 16384)^(1/9) = (0.0619)^(1/9) = 0.734 m.
Self GMD of B. With r' = 0.7788 × 0.04 = 0.03115 m: DsB = (r' × 4 × 4 × r')^(1/4) = √(4 × 0.03115) = 0.353 m.
Inductances: LA = 2 × 10⁻⁷ ln(7.16/0.734) = 2 × 10⁻⁷ × 2.278 = 4.56 × 10⁻⁷ H/m = 0.456 mH/km, and LB = 2 × 10⁻⁷ ln(7.16/0.353) = 2 × 10⁻⁷ × 3.010 = 6.02 × 10⁻⁷ H/m = 0.602 mH/km.
The loop inductance of the single-phase line is L = LA + LB = 1.06 mH/km (1.06 × 10⁻³ H per km of line). The return side has the higher inductance despite its larger strands because it has fewer of them and hence a smaller self GMD.
(b) Terminal voltage of the generator
Work in per unit on a 100 MVA base with voltage bases 11 kV, 220 kV and 66 kV in the three sections. Both transformers are rated at the base, so XT1 = 0.12 pu and XT2 = 0.10 pu. The line reactance on the 220 kV base is Xline = 100/(220²/100) = 100/484 = 0.2066 pu. Total series reactance X = 0.12 + 0.2066 + 0.10 = 0.4266 pu.
At the load bus V₂ = 60/66 = 0.9091 pu, taken as reference. The load is P = 0.6 pu at 0.9 pf lagging, so Q = 0.6 tan(cos⁻¹ 0.9) = 0.6 × 0.4843 = 0.2906 pu and the current is
I = (P − jQ)/V₂* = (0.6 − j0.2906)/0.9091 = 0.660 − j0.320 pu.
The generator terminal voltage on the 11 kV base is
V₁ = V₂ + jXI = 0.9091 + j0.4266(0.660 − j0.320) = 0.9091 + 0.1364 + j0.2816 = 1.0455 + j0.2816 pu,
|V₁| = √(1.0455² + 0.2816²) = 1.083 pu, i.e. 1.083 × 11 = 11.9 kV line-to-line, at an angle of 15.1° ahead of the load-bus voltage. The generator must be held at about 11.9 kV for the substation bus to stay at 60 kV.
(c) Arc in a circuit breaker and the restriking voltage
As the contacts begin to part, the area of contact shrinks to a few points, the current density and the resistance at these points rise sharply, and the metal there is heated to incandescence. Electrons are emitted from the hot cathode spot by thermionic emission, and, because the gap is at first only a few microns wide, the voltage gradient across it is very high and field emission adds to them. The emitted electrons, accelerated by the field, ionise the gas in the gap by collision; the resulting column of ionised gas is a good conductor and the current continues to flow through it as an arc. The arc is sustained because its own energy input (arc voltage times current) keeps the column hot enough for thermal ionisation to continue, the cathode spot stays hot enough for emission, and the surrounding medium is continuously ionised faster than it recombines. The arc is extinguished only when, at a natural current zero, the dielectric strength of the gap recovers faster than the voltage across it rises: this is the race between recovery voltage and dielectric recovery that decides breaker performance.
Restriking voltage. Consider a single phase of a solidly grounded system, with the source inductance L per phase (including the generator and transformer) and the stray capacitance C across the breaker contacts and to ground. Let the fault be cleared at a current zero; in an inductive circuit this occurs when the source voltage is at its peak, v = Vm, and for the few microseconds of the transient Vm can be taken as constant. After current zero the current through L flows into C, so, with the arc extinguished,
L di/dt + vc = Vm, i = C dvc/dt, giving LC d²vc/dt² + vc = Vm.
With vc(0) = 0 (the arc had short-circuited the capacitance) and i(0) = 0, the solution is
vc(t) = Vm(1 − cos ωn t), ωn = 1/√(LC).
This is the restriking voltage across the contacts: it oscillates at the natural frequency fn = 1/(2π√(LC)), reaches a peak of 2Vm at t = π√(LC), and its maximum rate of rise is Vm ωn (the average up to the first peak being 2Vm/(π√(LC))). Here Vm = √2 VL/√3 is the peak phase voltage, the neutral being solidly grounded. Damping resistance in the circuit reduces the peak below 2Vm.
(d) Mean square quantization error of a non-uniform quantizer
Divide the input range into intervals of widths Δᵢ, the ith interval having representation level yᵢ at its centre. Let f(x) be the probability density of the input amplitude. The mean square quantization error is
σq² = Σᵢ ∫(interval i) (x − yᵢ)² f(x) dx.
Because each Δᵢ is small compared with the excursion of the signal, f(x) is nearly constant over an interval and can be taken as its value fᵢ there. Writing e = x − yᵢ, which runs from −Δᵢ/2 to Δᵢ/2,
σq² ≈ Σᵢ fᵢ ∫(−Δᵢ/2 to Δᵢ/2) e² de = Σᵢ fᵢ Δᵢ³/12.
But fᵢΔᵢ is the probability pᵢ that the input lies in the ith interval, so
σq² ≈ (1/12) Σᵢ Δᵢ² pᵢ,
which is the required result. For a uniform quantizer every Δᵢ = Δ and Σ pᵢ = 1, and the expression reduces to the familiar Δ²/12; the non-uniform quantizer (a compander, for instance) makes Δᵢ small where pᵢ is large, which is how it lowers the error for signals such as speech that spend most of their time at small amplitudes.
(e) Syndromes and cosets in the standard array
Let C be an (n, k) linear block code with parity-check matrix H, so that a vector v is a code word if and only if its syndrome s = vHᵀ is zero. The standard array lists the 2^(n−k) cosets of C: each row is e + C = {e + c : c ∈ C} for a coset leader e, and the rows partition the space of all 2ⁿ vectors.
Same syndrome within a coset. Any vector in the coset e + C is of the form v = e + c with c ∈ C. Its syndrome is
s(v) = (e + c)Hᵀ = eHᵀ + cHᵀ = eHᵀ,
because cHᵀ = 0. Every vector in the row therefore has the same syndrome, that of its coset leader.
Uniqueness to the coset. Suppose two cosets e₁ + C and e₂ + C had the same syndrome, e₁Hᵀ = e₂Hᵀ. Then (e₁ − e₂)Hᵀ = 0, so e₁ − e₂ is a code word c, e₁ = e₂ + c, and e₁ lies in e₂ + C. Since cosets are either identical or disjoint, the two cosets are the same one. Hence distinct cosets have distinct syndromes.
There are 2^(n−k) cosets and 2^(n−k) possible syndromes, so the correspondence is one-to-one; this is what allows syndrome decoding: compute s = rHᵀ, look up the coset leader with that syndrome, and subtract it from r.
How this answer will be evaluated
What earns full marks: Complete working with correct method, units, and interpretation for all parts.
Evaluation rubric
Each sub-part is marked on its own, against the marks and word limit printed on the paper.
- (a) Inductance per unit length of the single-phase line. 10 marks
calculate— given → formula → substitution → result with units → interpretation
Must cover
- Calculate geometric mean radius (GMR) for each bundle
- Calculate geometric mean distance (GMD) between bundles
- Apply inductance formula L = 2π × 10⁻⁷ ln(GMD/GMR)
- Dm ≈ 7.16 m, DsA ≈ 0.734 m, DsB ≈ 0.353 m, loop inductance ≈ 1.06 mH/km
Loses marks
- Using radii instead of GMR in the final formula
- Unit conversion errors (cm to m)
Earns more
- Correct identification of 'go' and 'return' conductors
- Clear labeling of distances in the diagram
Extra mark
- Sketch of the conductor arrangement with dimensions
- (b) Terminal voltage of the synchronous generator. 10 marks
calculate— given → formula → substitution → result with units → interpretation
Must cover
- Convert all impedances to per-unit on a common base
- Calculate load current in per-unit or amperes
- Perform voltage drop calculation across line and transformers
- V1 ≈ 1.083 pu ≈ 11.9 kV (X total 0.4266 pu on 100 MVA)
Loses marks
- Ignoring transformer reactances in the calculation
- Incorrect base voltage selection for per-unit conversion
Earns more
- Use of phasor diagram for voltage drop calculation
- Explicit statement of base values used
Extra mark
- Calculation of voltage regulation percentage
- (c) Arc initiation/sustainment and restriking voltage expression. 10 marks
explain— definition/context → points in order → small example → short close
Must cover
- Explain arc initiation via thermionic emission or field emission
- Explain arc sustainment by thermal ionisation maintained by the arc energy input
- Derive restriking voltage expression for solidly grounded system
- State v(t) = Vm(1 − cos t/√(LC)), peak 2Vm at t = π√(LC)
Loses marks
- Confusing arc voltage with restriking voltage
- Derivation without stating the solidly grounded assumption
Earns more
- Mention of deionization for arc extinction
- Clear distinction between arc voltage and restriking voltage
Extra mark
- Sketch of voltage vs time showing restriking
- (d) Mean square quantization error for non-uniform quantizer. 10 marks
derive— given → assumptions → stepwise derivation → result → check
Must cover
- Define quantization error for the i-th interval
- Assume uniform distribution within each small interval
- Integrate error squared over each interval
- Sum over all intervals to get (1/12)ΣΔᵢ²pᵢ
Loses marks
- Skipping the integration step in the derivation
- Failing to justify the uniform distribution assumption
Earns more
- Explicit statement that Δᵢ is small compared to signal excursion
- Clear definition of pᵢ as probability in the i-th interval
Extra mark
- Comparison with uniform quantizer result
- (e) Same syndrome for all vectors in a coset. 10 marks
derive— given → assumptions → stepwise derivation → result → check
Must cover
- Define syndrome as Hxᵀ for a linear block code
- Prove that H(x₁-x₂)ᵀ = 0 for any codeword
- Conclude that Hx₁ᵀ = Hx₂ᵀ, so syndromes are equal
Loses marks
- Failing to show x₁-x₂ is a codeword
- Not using the property Hcᵀ = 0 for codewords
Earns more
- Explicit statement that the syndrome is unique to the coset
- Reference to the standard array structure
Extra mark
- Example with a specific code (e.g., Hamming code)
What "Solve" is asking you to do
Choose the method, then carry it through to a final answer. Identifying what kind of problem this is and why that method applies is the first thing marked; a correct figure arrived at invisibly earns almost nothing.
Structure that answers it
Given data and what is required → method chosen, with the reason it applies → set-up (equation, circuit, free body, trial balance) → working, step by step → answer with units and any condition of validity
Where marks are lost
Doing the middle steps mentally and writing only the result. In mathematics papers, a further loss comes from giving a decimal where the exact value in surds or fractions was wanted, or from skipping the justification a part explicitly asks for.
Practice this exact question
Write your answer and it is marked point by point against the model answer above — what you covered, what you missed, what you got wrong.
Evaluate my answer →More from Electrical Engineering 2022 Paper II
- Q2 (a) A unity feedback system is shown in the figure below. Determine the range of α for wh…
- Q3 (a) (i) The figure below shows a schematic diagram of shunt ohmmeter. It consists of a ba…
- Q4 (a) (i) List various interrupts in microprocessor 8085 in order of decreasing priority. S…
- Q5 (a) Determine the inductance of a single-phase transmission line consisting of three cond…
- Q6 (a) A three-phase, 50 Hz transmission line is 400 km long. The voltage at the sending end…
- Q7 (a) The figure below shows the encoder for a rate r = 1/2, constraint length k = 4 convol…
- Q8 (a) Answer the following : (i) Write the recommended expression for time-current relation…