Electrical Engineering 2022 Paper II 50 marks Calculate

Paper II — Q8

(a) Answer the following : (i) Write the recommended expression for time-current relationship of standard IDMT relay and draw…

(a)

Answer the following :

(i)

Write the recommended expression for time-current relationship of standard IDMT relay and draw its characteristic curve. Why is this type of relay commonly used for protection of electrical machines?

(ii)

Draw the circuit arrangements for connecting earth fault relay in 3φ supply and explain its working for core balance current transformer as well as for three CT system. 20 marks

(b)

The received signal in a binary communication system that employs antipodal signals is r(t) = s(t) + n(t), where s(t) is shown in the figure below and n(t) is AWGN with power spectral density N₀/2 W/Hz :

[Figure: s(t) consists of two rectangular pulses of height A, one from t = 0 to 1 and one from t = 2 to 3, zero elsewhere]

(i)

Sketch the impulse response of the filter matched to s(t).

(ii)

Sketch the output of the matched filter when the input is s(t).

(iii)

Determine the variance of the noise at the output of the matched filter at t = 3.

(iv)

Determine the probability of error as a function of A and N₀. 20 marks

(c)

Find the steady-state power limit of a system consisting of a generator having equivalent reactance of 0.5 pu, connected to an infinite bus through a series reactance of 1.0 pu. The terminal voltage of the generator is held at 1.20 pu and the voltage of the infinite bus at 1.0 pu. 10 marks

हिंदी में प्रश्न पढ़ें
(a)

निम्नलिखित के उत्तर दीजिए :

(i)

मानक आईडीएमटी रिले के लिए अनुमन्य समय-धारा सम्बन्ध का व्यंजक लिखिए तथा इसका लक्षणिक वक्र आरेखित कीजिए। सामान्यतः कौन विद्युत यंत्रों के संरक्षण के लिए इस प्रकार की रिले का प्रयोग किया जाता है?

(ii)

त्रि-कला प्रदाय में भू-संपर्क त्रुटि (अर्थ फाल्ट) रिले को संयोजित करने के लिए परिपथ व्यवस्था को आरेखित कीजिए तथा कोर संतुलन धारा परिणामित्र व तीन धारा परिणामित्र प्रणाली के लिए इसकी कार्यविधि समझाइए। (20 अंक)

(b)

एंटीपोडल संकेतों का प्रयोग करने वाली एक द्वि-आधारी (बाइनरी) संचार प्रणाली में प्राप्त संकेत r(t) = s(t) + n(t) है, जहाँ s(t) नीचे चित्र में प्रदर्शित है और n(t) ए. डब्ल्यू. जी. एन. है, जिसका शक्ति वर्णक्रम घनत्व N₀/2 W/Hz है :

[figure]

(i)

s(t) से सुमेलित छंकर (फ़िल्टर) की आवेग प्रतिक्रिया आरेखित कीजिए।

(ii)

जब निवेश s(t) हो, तो सुमेलित छंकर का निर्गत आरेखित कीजिए।

(iii)

t = 3 पर सुमेलित छंकर के निर्गम पर शब का विभेद (वैरेंस) ज्ञात कीजिए।

(iv)

A और N₀ के फलन के रूप में त्रुटि की प्रायिकता ज्ञात कीजिए। (20 अंक)

(c)

अनन्त बस पर श्रेणी में 1.0 pu के प्रतिघात से होकर जुड़े हुए 0.5 pu तुल्य प्रतिघात वाले एक जनरेटर को समाहित करती हुई एक प्रणाली की स्थिर-अवस्था शक्ति सीमा ज्ञात कीजिए। जनरेटर की अन्तस्थ वोल्टता को 1.20 pu पर तथा अनन्त बस की वोल्टता को 1.0 pu पर रखा गया है। (10 अंक)

Q8 of the 2022 UPSC Mains Electrical Engineering Paper II, as printed
The question as printed in the 2022 Electrical Engineering paper

The figure this question refers to, in words

The question paper is a scan and the diagram did not survive as text. This is the figure as read from the original page — every component, value and label — so the question can be worked from the text below.

(b) s(t): rectangular pulses of amplitude A on 0 to 1 and 2 to 3, zero elsewhere.

Model answer

Drafted with AI by UPSC Answer Check against this question's marking rubric, to the expected length. UPSC does not publish answers for Mains — this is one way to score well, not an official key. How we build rubrics and answers.

(a)(i) The IDMT relay

The standard inverse definite minimum time characteristic recommended by IEC 60255 (and IS 3231) is

t = TMS × 0.14/[(PSM)^0.02 − 1] seconds,

where PSM, the plug-setting multiplier, is the fault current divided by the relay's current setting (I/Is), and TMS is the time-multiplier setting (0.1 to 1.0), which scales the whole curve. The related IEC curves have the same form with other constants: very inverse 13.5/(PSM − 1) and extremely inverse 80/(PSM² − 1).

The characteristic curve is drawn with PSM (1 to 20) on a logarithmic horizontal axis and operating time on the vertical axis. It starts at infinity just above PSM = 1, falls steeply, and flattens: with TMS = 1 the times are about 10 s at PSM = 2, 4.3 s at PSM = 5, 3.0 s at PSM = 10 and 2.3 s at PSM = 20. Above about PSM = 20 the curve becomes almost flat (the 'definite minimum time' part), because the electromagnet saturates in an electromechanical relay and the setting is deliberately limited in a numerical one. Lower TMS values give a family of curves of the same shape below it.

Diagram: IDMT relay characteristic

It suits electrical machines because a machine's own withstand curve is inverse: overload heating follows I²t, so a small overload can be tolerated for minutes while a heavy fault must be cleared in a fraction of a second. The IDMT curve tracks this thermal limit, rides through starting currents and short transient overloads without tripping, and its definite-minimum-time tail keeps the operating time predictable for heavy faults so that it grades with the up-stream and down-stream protection. The two settings (plug and time multiplier) make the relay easy to coordinate over a whole feeder.

(a)(ii) Earth-fault relay connections

Core-balance current transformer. All three phase conductors of the circuit pass together through the window of a single ring-type CT; the relay is connected across its secondary. Under normal load or a phase-to-phase fault the three currents sum to zero, the net flux in the core is zero and the relay carries no current. When an earth fault occurs on the protected circuit, the fault current returns through the earth and not through the window, so the vector sum of the three conductor currents is no longer zero; the residual current sets up flux in the core, a secondary current flows and the relay operates. Because the CT sees the residual directly and there is no summation of three separate CT errors, the setting can be very sensitive (a few per cent of full load); it is the usual arrangement for cables, motors and generators. The cable sheath earthing lead must be brought back through the window so that sheath current does not cause false operation.

Three-CT residual connection. A CT is fitted in each phase, the three secondaries are connected in star, and the earth-fault relay is placed in the common return (the neutral wire of the star). The current in the relay is the sum of the three secondary currents, i.e. the residual current 3I₀. Under balanced conditions and phase faults this sum is zero apart from the mismatch between the CTs, so the relay stays put; an earth fault produces a residual current and the relay operates. Phase-fault overcurrent relays may be connected in the same CT secondaries, one in each phase, with the earth-fault relay in the residual lead. The setting cannot be made as low as with a core-balance CT because the spill current from CT errors under heavy through-faults would cause maloperation; a stabilising resistor or a higher setting (10–40%) is used.

Diagram: Earth-fault relay connections: core-balance CT and three-CT residual

(b) The matched filter and the antipodal system

The signal s(t) is a pair of rectangular pulses of height A, one from t = 0 to 1 and one from t = 2 to 3, with a gap between them; its duration is T = 3 and its energy is E = ∫s²(t) dt = A²(1 + 1) = 2A².

(i) Impulse response. The filter matched to s(t) has h(t) = s(T − t) = s(3 − t). Reflecting the signal about t = 1.5 gives the same shape: h(t) = A for 0 ≤ t < 1 and 2 ≤ t < 3, and zero elsewhere. The sketch is s(t) itself.

(ii) Output for input s(t). The output is y(t) = s(t) * h(t), which equals the autocorrelation of s(t) shifted so that its peak falls at t = T = 3. The autocorrelation of two unit pulses separated by a gap is a large triangle of height 2A² (both pulses overlapping their own images) with two smaller triangles of height A² on either side (one pulse overlapping the other's image). The sketch therefore rises linearly from zero at t = 0 to A² at t = 1, falls to zero at t = 2, rises to the peak 2A² at t = 3, falls to zero at t = 4, rises to A² at t = 5 and returns to zero at t = 6. The sampling instant is t = 3, where y(3) = E = 2A².

Diagram: Matched filter for a two-pulse antipodal signal

(iii) Noise variance at t = 3. For white noise of spectral density N₀/2 through a filter with impulse response h(t), the output noise variance is

σ² = (N₀/2) ∫h²(t) dt = (N₀/2) × 2A² = N₀A².

(iv) Probability of error. The antipodal system sends s(t) for one symbol and −s(t) for the other, so the two sampled outputs are ±E = ±2A² with noise of variance σ² = N₀A². The optimum threshold is zero and

Pe = Q(E/σ) = Q(2A²/(A√N₀)) = Q(2A/√N₀) = Q(√(2E/N₀)) = ½ erfc(√(E/N₀)) = ½ erfc(A√(2/N₀)).

The result depends only on the energy per bit, not on the shape of s(t): the gap in the pulse costs nothing so long as the receiver is matched to it.

(c) Steady-state power limit

Let V = 1.0∠0° pu be the infinite-bus voltage, E the internal e.m.f. behind the generator reactance Xd = 0.5 pu, and X = 1.0 pu the series reactance, so that the total transfer reactance is 1.5 pu. The steady-state power limit is reached when the angle between E and V is 90°, so put E = |E|∠90° = j|E|.

The terminal voltage is the point between the two reactances. With no load tapped there, the current is the same in both, and Vt divides the voltage difference in the ratio of the reactances:

Vt = (E × X + V × Xd)/(Xd + X) = (j|E| × 1.0 + 1.0 × 0.5)/1.5 = (0.5 + j|E|)/1.5.

The terminal voltage is held at 1.20 pu, so |0.5 + j|E|| = 1.8, |E|² = 1.8² − 0.5² = 2.99, |E| = 1.729 pu.

The steady-state power limit is then

Pmax = |E||V|/(Xd + X) = 1.729 × 1.0/1.5 = 1.153 pu.

At this limit the terminal voltage leads the infinite bus by tan⁻¹(1.729/0.5) = 73.9°, and the power delivered through the line, |Vt||V| sin 73.9°/1.0 = 1.2 × 0.961 = 1.153 pu, checks. Because the limit is set by a 90° angle between E and V rather than across the line alone, it is less than the 1.2 × 1.0/1.0 = 1.2 pu that the line alone could carry at a line angle of 90°.

How this answer will be evaluated

What earns full marks: Complete derivations, correct diagrams, and clear physical interpretation of all results.

Evaluation rubric

Each sub-part is marked on its own, against the marks and word limit printed on the paper.

  1. (a) IDMT relay expression and curve; Earth fault relay circuit and working. 20 marks

    describe— define → structure or process in order → labelled diagram → significance

    Must cover

    • IDMT time-current expression (e.g., IEC/BS standard)
    • Characteristic curve of IDMT relay
    • Reason for IDMT use in machine protection
    • Circuit diagram for earth fault relay (3-phase)

    Loses marks

    • Missing IDMT curve
    • Confusing phase fault with earth fault relay logic

    Earns more

    • Explanation of core balance CT working
    • Explanation of three CT system working
    • Mention of zero-sequence current detection

    Extra mark

    • Comparison of core balance vs 3-CT sensitivity
  2. (b) Matched filter analysis for antipodal signals: impulse response, output, noise variance, and error probability. 20 marks

    calculate— given → formula → substitution → result with units → interpretation

    Must cover

    • Impulse response h(t) = s(T-t) sketch
    • Matched filter output y(t) sketch
    • Noise variance at t = 3: σ² = (N₀/2)·2A² = N₀A²
    • Pe = Q(2A/√N₀) = Q(√(2E/N₀)) with E = 2A²

    Loses marks

    • Incorrect time reversal for matched filter
    • Missing factor of 2 in noise variance

    Earns more

    • Correct energy calculation of s(t)
    • Proper handling of AWGN PSD N0/2
    • Clear labeling of time axis in sketches

    Extra mark

    • Derivation of the Q-function argument
  3. (c) Steady-state power limit of a generator-infinite bus system. 10 marks

    calculate— given → formula → substitution → result with units → interpretation

    Must cover

    • Equivalent circuit diagram with reactances
    • Total reactance calculation (0.5 + 1.0 pu)
    • Power limit formula P = (E*V/X)sin(delta)
    • |E| ≈ 1.729 pu from Vt = 1.2, Pmax = 1.729/1.5 ≈ 1.153 pu

    Loses marks

    • Ignoring generator internal reactance
    • Using terminal voltage as internal EMF

    Earns more

    • Correct per-unit system usage
    • Clear identification of internal EMF vs terminal voltage

    Extra mark

    • Phasor diagram of the system
What "Calculate" is asking you to do

Apply the standard formula or schedule to data the question has already supplied — a table of readings, cost records, a balance sheet — and produce the number. The method is rarely in doubt; the marks sit in the named intermediate quantities, each of which has to appear as a labelled line.

Structure that answers it

Data as given → formula or standard treatment, named → substitution → each intermediate, labelled → result with units

Where marks are lost

Omitting an intermediate the marking scheme pays for separately, or rounding at an intermediate line so the final figure drifts. In commerce and accountancy, any figure in a statement that no numbered working note supports is treated as unearned.

All UPSC directive words, compared →

Practice this exact question

Write your answer and it is marked point by point against the model answer above — what you covered, what you missed, what you got wrong.

Evaluate my answer →

More from Electrical Engineering 2022 Paper II

Write this answer and get it marked in about 20 seconds

Free account: 5 AI evaluations a month, marked against the rubric above.

Start free

Already have an account? Log in