Q1 50M Compulsory solve AC voltage controller, control systems, electrical machines, electric traction, Fourier transform
(a) A single-phase AC voltage controller is feeding a resistive load of 26·45 Ω from an AC source of 230 V, 50 Hz. Compute the firing angle to deliver 1000 W to the load. Also compute the p.f. at which this power is delivered. Draw a neat circuit diagram and waveforms of voltage at load terminals with current flowing in the load. 12 marks
(b) An open-loop system G(s) = 1/s²(τs+1) is placed in cascade with a proportional and derivative controller K(s) = (1+Tds). If their unity feedback closed-loop system oscillates at a frequency of √2 rad/second, find the ranges/values of the system and controller parameters, i.e., ranges/values of K, Td and τ. 12 marks
(c) Determine the mechanical time constant of rotor of an electrical machine in terms of its moment of inertia J kg-m² and windage cum friction coefficient f N-m/rad/s. Also explain the method to determine mechanical time constant experimentally in laboratory. 12 marks
(d) An electric train running between two stations A and B, 10 km apart and maintained at voltages 550 V and 500 V respectively, draws a constant current of 600 A. The resistance for both go and return conductors is 0·04 Ω/km. Find the point of minimum potential between the stations, the voltage at that point and currents drawn from both the stations at that point. 12 marks
(e) The continuous-time Fourier transform (CTFT) of a square pulse defined by x(t) = 1 for −0·5 ≤ t ≤ 0·5 is given by X(ω) = sin(ω/2)/(ω/2). Use the properties of CTFT and synthesize the equation, and find the CTFT of the following signals y(t) and z(t):
y(t) = {2, for 0 ≤ t < 1; −2, for 1 ≤ t ≤ 2; 0, elsewhere
[diagram of z(t) showing triangular pulse with peak 2 at t=1, zero at t=0 and t=2]
12 marks
Answer approach & key points
Solve all five sub-parts systematically, allocating approximately 20% time to each part given equal 12-mark weighting. Begin with clear circuit diagrams and waveforms for (a), proceed through control system analysis for (b), derive mechanical time constant expression for (c), apply Kirchhoff's laws for traction problem (d), and apply CTFT properties for (e). Present derivations stepwise with final boxed answers for each sub-part.
- Part (a): Correct firing angle calculation using P = (V²/2πR)(2π - α + sin2α/2) = 1000W, yielding α ≈ 90°; power factor = √(P/VA) = √(1000×26.45/230²); circuit diagram showing SCR pair with resistive load; voltage and current waveforms showing conduction from α to π
- Part (b): Characteristic equation 1 + G(s)K(s) = 0 → τs³ + s² + KTd s + K = 0; Routh-Hurwitz criterion application; oscillation condition: auxiliary equation roots at s = ±j√2 yielding K = 2, Td = τ = 1/√2 or equivalent valid ranges
- Part (c): Mechanical time constant τm = J/f seconds; experimental method: run machine at no-load, disconnect supply, measure speed decay time to 36.8% of initial value using tachometer and stopwatch; or use retardation test plotting ω vs t on semilog paper
- Part (d): Set up voltage distribution V(x) = VA - I·r·x - (VA-VB-I·r·L)·x/L for x from A; find dV/dx = 0 for minimum potential point; calculate currents IA and IB using current continuity at minimum potential point
- Part (e): Express y(t) as 2[u(t)-2u(t-1)+u(t-2)] using time-shift and linearity; apply scaling and shifting to get Y(ω) = 2e^(-jω/2)[sin(ω/2)/(ω/2)][1-e^(-jω)]; for z(t) as triangular pulse, use convolution of rectangular pulses or differentiation property
Q2 50M calculate PWM inverters, induction generators, power system fault analysis
(a) A single-phase full bridge inverter is used to produce a 50 Hz voltage across a series R-L load (R = 10 Ω and L = 20 mH) using bipolar PWM. The DC input to the bridge is 380 V, the amplitude modulation ratio mₐ = 0·8 and frequency modulation ratio mƒ = 21. Consider dominant harmonics to be frequency dominant and its nearby side frequencies (both sides). Assume normalized Fourier coefficient for mₐ = 0·8 to be 82% for dominant harmonic frequency and 22% for the nearby side frequencies. Determine—
(i) amplitude of 50 Hz component of output voltage and current;
(ii) power absorbed by the load resistor;
(iii) THD of the load current.
Also compare the amplitude of 50 Hz component of output voltage with square wave and quasi-square wave output. 20 marks
(b) A 3-phase, 6-pole, 460 V, 50 Hz induction generator operates at 480 V. The generator has its rated output power of 20 kW. It is driven by a turbine at a speed of 1015 r.p.m. The generator has the following electrical parameters: R₁ = 0·2 Ω, R₂ = 0·15 Ω, Rₛₕ = 320 Ω, X₁ = 1·2 Ω, X₂ = 1·29 Ω, Xₘ = 42 Ω. Find the active power delivered by the generator and reactive power it requires from the system to operate. 20 marks
(c) (i) Under what condition a single line-to-ground fault at the terminals of a generator can be more severe than a 3-phase symmetrical fault at the same location?
(ii) A 3-phase power system is represented by one-line diagram as shown in the figure below: The ratings of the equipments are the following: Generator G: 15 MVA, 6·6 kV, X₁ = 15%, X₂ = 10%; Transformers: 15 MVA, 6·6 kV delta/33 kV star, X₁ = X₂ = X₀ = 6%; Line reactance: X₁ = X₂ = 2 Ω and X₀ = 6 Ω. Find the fault current for a ground fault on one of the bus bars at B. 20 marks
Answer approach & key points
Calculate all numerical quantities demanded across the three parts, allocating approximately 35% time to part (a) given its multi-step PWM analysis and comparison requirement, 30% to part (b) for induction generator power flow calculations, and 35% to part (c) for sequence network construction and fault analysis. Begin each part with the appropriate formula statement, show systematic substitution, and conclude with physical interpretation of results.
- Part (a): Correct application of bipolar PWM fundamental voltage formula V₁ = mₐ × Vdc and harmonic voltage calculation using normalized Fourier coefficients; impedance calculation at dominant harmonic frequency (mf × f₁ = 1050 Hz) and side frequencies
- Part (a): THD calculation using Iₕ/I₁ ratio summation for identified harmonics, and explicit comparison table showing V₁(50Hz) for PWM (304V), square wave (4Vdc/π = 484V), and quasi-square wave with pulse width δ
- Part (b): Correct determination of slip s = (Ns - N)/Ns = -0.01 for generator operation; accurate calculation of Thevenin equivalent or direct impedance method for rotor circuit; separation of air-gap power into active and reactive components
- Part (b): Proper accounting for core loss resistance Rsh and magnetizing branch in power calculations; correct sign convention for generator operation (P delivered positive, Q absorbed positive)
- Part (c)(i): Clear statement that single line-to-ground fault exceeds 3-phase fault severity when X₀ < X₁ (typically with solidly grounded neutral or low X₀/X₁ ratio), making I(LG) = 3E/(2X₁+X₀) > I(3φ) = E/X₁
- Part (c)(ii): Correct sequence network interconnection for single line-to-ground fault (series connection of positive, negative, zero sequence); proper base conversion (15 MVA, 6.6 kV base) and per-unit calculations for transformer, line impedances; final fault current in amperes at 33 kV bus B
Q3 50M solve Circuit analysis, signal processing, root locus
(a) For the circuit shown below, calculate the output voltage :
R₁ = 1 kΩ R₂ = 2 kΩ R₃ = 3 kΩ
R₄ = 10 kΩ R₅ = 10 kΩ R₆ = 100 kΩ
V₁ = -1 V V₂ = -2 V V₃ = 8 V
(b) A signal xₐ(t) is band-limited to the range 900 Hz ≤ f ≤ 1100 Hz (assume the shape of an isosceles triangle for continuous Fourier transform and |Xₐ(f)| = 1 and f = 1000 Hz). It is used as an input to the system shown below :
In this system, H(ω) is a low-pass filter with a discrete cut-off frequency equivalent to f꜀ = 125 Hz (normalized w.r.t. the sample rate at the point in the block diagram). Determine and sketch the spectra of X(ωₓ), W(ωᵥ), V(ωᵥ) and Y(ωᵧ) w.r.t. ωₓ, ωᵥ, ωᵥ and ωᵧ respectively for -π < ω < π.
(c) For the system shown in the figure below, the step response of G(s) is given by (1·5 - 2e⁻ᵗ + 0·5e⁻²ᵗ)u(t) and K(s) is the integral controller with K(s) = K/s. Sketch the approximate root locus of the closed-loop system poles as K varies from 0 to ∞. Also calculate the real part of poles when K becomes ∞ :
Answer approach & key points
Solve this multi-part numerical problem by allocating approximately 3 marks worth of effort to each sub-part. For (a), apply superposition or nodal analysis to find the op-amp output voltage. For (b), trace the spectral transformations through sampling, filtering, and decimation stages with clear frequency axis annotations. For (c), derive G(s) from the given step response, then construct the root locus for the integral-controlled system showing asymptotes and breakaway points. Present derivations first, followed by numerical results and clearly labeled sketches.
- Part (a): Correct application of superposition theorem or virtual ground concept for the multi-input op-amp circuit; accurate calculation of contribution from each voltage source V₁, V₂, V₃
- Part (a): Proper handling of resistor ratios (R₄/R₁, R₄/R₂, R₄/R₃) with correct polarity for inverting summer configuration; final output voltage calculation with sign
- Part (b): Correct determination of sampling rate and resulting spectral replicas; sketch of X(ωₓ) showing triangular spectrum centered at ω = 0.2π (normalized) with replicas at 2π intervals
- Part (b): Accurate depiction of low-pass filtering effect on W(ωᵥ), decimation-induced spectral stretching in V(ωᵥ), and final output Y(ωᵧ) with proper frequency axis scaling
- Part (c): Derivation of G(s) = 3(s+1)/[s(s+2)] from the given step response via Laplace transform; identification of poles at s = 0, -2 and zero at s = -1
- Part (c): Construction of root locus showing: branches starting at s = 0 and s = -2, meeting at breakaway point, then becoming complex; asymptotes at ±90°; real part of poles at -1.5 when K → ∞
Q4 50M solve Cable grading, induction motor control, transformer magnetizing current
(a) (i) What do you mean by grading of cables? What are the methods of grading?
(ii) Derive the condition for minimum value of gradient at the surface of the conductor.
(iii) Determine the economic overall diameter of a single-core cable metal sheathed for a working voltage of 75 kV, if the dielectric strength of the insulating material is 60 kV/cm.
(b) A 400 V, 50 Hz, 6-pole, 960 r.p.m., Y-connected induction motor has the following parameters per phase referred to stator :
r₁ = 0·4 Ω; r₂' = 0·2 Ω; x₁ = x₂' = 1·5 Ω; Xₘ = 30 Ω
The motor is controlled by a variable frequency inverter at a constant flux of rated value for operation below synchronous speed, while in super-synchronous operation region flux is weakened by keeping voltage constant at rated value. Assume straight line for torque vs. slip characteristics for slip s < sₘ (motor region) and s > sₘ' (generator region). The connected load on the shaft is constant torque type.
Calculate the inverter frequency and current drawn by the stator when torque on the shaft is half-rated while motoring at 500 r.p.m.
(c) Why is the waveshape of magnetizing current of a transformer non-linear? Explain the phenomenon of in-rush magnetizing current and derive its expression in terms of α, the angle of the voltage sinusoid at t = 0 and Φᵣ, the residual core flux at t = 0.
Use the graph sheet to show non-linearity of current from the assumed Φ-i diagram of magnetic core of the transformer.
Answer approach & key points
This is a multi-part numerical and theoretical problem requiring systematic solving. Begin with part (a) on cable grading: define grading, derive the condition for minimum gradient using calculus on the electric field expression, then calculate economic diameter using the optimal radius ratio condition. For part (b), apply variable frequency control principles: first determine rated torque and slip, then use constant V/f control below synchronous speed to find inverter frequency at 500 rpm, and calculate stator current using the equivalent circuit with modified frequency parameters. For part (c), explain core saturation physics, derive the inrush current expression from flux balance equation considering residual flux and switching angle, and sketch the Φ-i curve showing non-linear magnetization. Allocate approximately 35% time to (a), 40% to (b), and 25% to (c) based on computational complexity.
- Part (a)(i): Definition of cable grading as equalizing dielectric stress; identification of capacitance grading (using multiple dielectrics) and intersheath grading (using intermediate conducting layers) methods
- Part (a)(ii): Derivation showing E_max is minimized when ln(R/r) = 1, i.e., R/r = e ≈ 2.718, giving optimal conductor-to-sheath radius ratio
- Part (a)(iii): Calculation of economic diameter using g_max = V/(r·ln(R/r)) with ln(R/r)=1, yielding overall diameter ≈ 4.06 cm for 75 kV working voltage
- Part (b): Determination of rated torque from synchronous speed (1000 rpm) and rated slip; application of constant flux (V/f) control to find inverter frequency ≈ 25 Hz at 500 rpm; calculation of stator current ≈ 12-14 A using modified equivalent circuit parameters
- Part (c): Explanation of non-linear magnetizing current due to saturation in B-H curve; derivation of inrush current i = (V_m/ωL)(cosα - cos(ωt+α)) + Φ_r/L showing DC offset; graph showing peaked waveform with harmonic content
Q5 50M Compulsory solve DC motor drives, transformers, AM modulation, control systems, protective relaying
(a) A DC motor has an armature resistance of 0·5 Ω and Kφ of 3 Vs. The motor is driven by a single-phase thyristorized full converter. The input to the converter is an AC source of 230 V, 50 Hz. The motor is used as a prime mover of a forklift. In the upward direction, the mechanical load is 69 Nm and the triggering angle is α = 15°. In the downward direction, the load torque is 180 Nm. Calculate the triggering angle required to keep the downward speed equal in magnitude to upward speed. Assume continuous motor current for all operation. Also calculate the triggering angle to keep the motor at holding position while it was moving upward. 12 marks
(b) The primary side of an ideal transformer (having 400 turns in primary winding and 720 turns in secondary winding) is excited by a 1000 V, 50 Hz AC source. The secondary of the transformer is connected to a resistive load of 80 kW. There is one tapping in secondary winding at 480 turns and this tapping is supplying a pure inductive load of 100 kVA. Determine the primary current and its power factor. 12 marks
(c) (i) Obtain an expression for the total average power of a sinusoidal AM wave
v_c = V_c sin ω_c t
v_m = V_m sin ω_m t
(ii) An AM transmitter broadcasts a carrier power of 100 kW. Determine the radiated power at the amplitude modulation index of 0·8. 12 marks
(d) Given a unity feedback system with G(s) = K/s(s+a) as shown in the figure :
(i) Find the values of K and a, when the closed-loop system has K_v = 100 and admits 20% peak overshoot.
(ii) Find the values of K and a, when the closed-loop system has settling time (2% tolerance band) of 2 seconds and admits 10% peak overshoot. 12 marks
(e) Two relays R_1 and R_2 are connected in two sections of a feeder as shown in the following figure. CTs are of ratio 1000/5. The plug setting of relay R_1 is 100% and of R_2 is 125%. The operating time characteristics of the relay is given in the following table :
Operating time characteristics for TMS = 1
PSM | 2 | 4 | 5 | 8 | 10 | 20
Operating time (seconds) | 10 | 5 | 4 | 3 | 2·8 | 2·4
The time multiplier setting of the relay R_1 is 0·3. The time grading scheme has a discriminative margin of 0·5 s between the relays. A three-phase short circuit at F results in a fault current of 5000 A. Find the actual operating time of R_1 and R_2. What is the time multiplier setting (TMS) of R_2? 12 marks
Answer approach & key points
Solve all five numerical sub-parts systematically, allocating approximately 20% time to each part given equal 12-mark weighting. Begin with clear identification of given data and required unknowns for each sub-part. Present derivations first where asked (AM power expression in c-i, control system parameters in d-i and d-ii), followed by numerical substitutions and final answers with proper units. For relay coordination in part (e), clearly show PSM calculations and time grading logic.
- Part (a): Apply full converter voltage equation V_a = (2V_m/π)cosα for upward motion; use torque-speed relation T = KφI_a and back EMF E_b = Kφω to find speed; for downward motion with regenerative braking, determine α for same speed magnitude; calculate holding angle when E_b = 0
- Part (b): Calculate secondary voltages using turns ratio; determine currents in each secondary section using S = VI; apply ampere-turn balance equation N_1I_1 = N_2I_2 + N_3I_3 with proper phase consideration for inductive load; compute primary current magnitude and power factor
- Part (c): Derive AM wave expression v(t) = V_c[1 + m sin(ω_m t)]sin(ω_c t); expand and identify carrier, upper and lower sideband components; integrate over period to obtain average power P_avg = P_c(1 + m²/2); substitute m = 0.8 to find radiated power
- Part (d): Use standard second-order system relations: K_v = K/a, ζ from overshoot formula %OS = exp(-ζπ/√(1-ζ²)) × 100, settling time t_s = 4/(ζω_n); solve simultaneous equations for K and a in both cases
- Part (e): Calculate PSM for both relays as I_fault/I_pickup; interpolate operating time from given table for TMS=1; apply actual TMS for R_1; ensure time grading margin of 0.5s between R_2 and R_1; back-calculate TMS for R_2
Q6 50M calculate DC motor starter, transmission line parameters, boost converter design
(a) A 20 kW, 500 V DC shunt motor (having 90% full-load efficiency) has 40% armature copper losses of its full-load losses. Calculate the resistance values of a 4-section starter suitable for limiting starting current between 120% to 200% of full-load current. Assume field resistance of 250 Ω. 20 marks
(b) (i) Differentiate between characteristic impedance and surge impedance of a line. What do you mean by surge impedance loading (SIL) of a transmission line?
(ii) A three-phase, 50 Hz transmission line is 400 km long. The voltage at the sending end is 220 kV. The line parameters are r = 0·125 ohm/km, x = 0·4 ohm/km and y = 2·8×10⁻⁶ mho/km. Find the sending-end current and receiving-end voltage when there is no load on the line. Make a comment on the value of receiving-end voltage. 20 marks
(c) A boost converter is required to have an output voltage of 48 V and supply a load current of 5 A. The input varies from 12 V–24 V. A control circuit adjusts the duty ratio to keep the output voltage constant. Select the switching frequency to be 200 kHz. Determine a value of inductor such that the variation in inductor current is no more than 40% of average inductor current for all operation. Prescribe a suitable value of capacitor such that output ripple is no more than 2%. 20 marks
Answer approach & key points
This is a calculation-heavy question demanding precise numerical work across three distinct domains. Begin with part (a) by first computing full-load current and losses, then establishing the current limits for starter design, and systematically deriving the four resistance sections. For part (b), first differentiate the impedance concepts conceptually, then apply the long-line ABCD parameters (or nominal π approximation) for the 400 km line to find sending-end current and receiving-end voltage under no-load, commenting on the Ferranti effect. For part (c), design the boost converter by calculating duty ratios for both input extremes, determining inductor value for worst-case ripple condition, and sizing capacitor for output voltage ripple. Allocate approximately 35% time to (a), 35% to (b), and 30% to (c), ensuring all derivations are shown stepwise with proper units.
- Part (a): Calculation of full-load current (40 A), total losses (2222.22 W), armature copper loss (888.89 W), armature resistance (0.556 Ω), and starter resistances R1-R4 (2.083 Ω, 1.25 Ω, 0.75 Ω, 0.45 Ω approximately) with current limits 48-80 A
- Part (b)(i): Clear distinction that characteristic impedance Zc = √(z/y) is frequency-dependent complex quantity while surge impedance Zs = √(L/C) is real and lossless; SIL = V²/Zs where natural power flow occurs at unity power factor
- Part (b)(ii): Application of long transmission line equations or nominal π method with ABCD parameters for 400 km line; calculation of sending-end current (approximately 180-200 A) and receiving-end voltage (approximately 245-260 kV, higher than sending end due to Ferranti effect)
- Part (c): Duty ratio calculation for Vin=12V (D=0.75) and Vin=24V (D=0.5); inductor selection based on worst-case ripple at D=0.5 or D=0.75 with ΔIL ≤ 40% of IL; L ≈ 45-60 μH; capacitor for 2% ripple (≈960V peak-to-peak at 48V means 0.96V ripple) yielding C ≈ 10-15 μF
- Practical interpretation: Comment on starter step transition currents, Ferranti effect significance for 400 km Indian transmission corridors (e.g., HVDC back-to-back stations), and converter continuous conduction mode verification
Q7 50M solve AC/DC converter, electromechanical systems, circuit breakers
(a) A full-controlled full-wave bridge AC/DC converter is fed from a single-phase, 230 V, 50 Hz supply, and is in turn feeding to an R-L load (R = 10 Ω and L = 100 mH). The firing angle α = 60°. Investigate whether load current remains continuous or not. Compute r.m.s. load current considering only the dominant harmonic, and determine the power absorbed by the load. Also compute voltage ripple factor. 20 marks
(b) For the electromechanical system shown below, the air-gap flux density under steady-state operating condition is given by
B(t) = Bₘ sin ωt
Find the instantaneous coil voltage and current along with force of magnetic field origin : 20 marks
(c) (i) In case of a circuit breaker, define the terms 'restriking voltage' and 'RRRV', and express their maximum values in terms of system voltage.
(ii) Which circuit breaker is preferred for voltages 132 kV and above?
(iii) In a 132 kV system, the reactance per phase up to the location of circuit breaker is 5 Ω and capacitance to earth is 0·03 µF. Calculate the maximum value of restriking voltage, the maximum value of RRRV and frequency of transient oscillation. 20 marks
Answer approach & key points
Solve this multi-part numerical problem by allocating approximately 35% time to part (a) due to its computational complexity involving harmonic analysis, 30% to part (b) for deriving instantaneous electromagnetic quantities, and 35% to part (c) covering circuit breaker theory and transient calculations. Begin with clear problem statements for each part, show complete derivations with intermediate steps, and conclude with physically meaningful interpretations of results.
- Part (a): Calculate extinction angle β using transcendental equation for R-L load, verify continuity condition (β > π+α), compute dominant harmonic (2nd harmonic) RMS current using Fourier analysis, determine power absorbed, and derive voltage ripple factor
- Part (a): Apply correct formula for ripple factor considering only dominant harmonic component in the output voltage
- Part (b): Derive instantaneous coil voltage using Faraday's law (e = N dΦ/dt), determine current considering coil resistance/inductance, and compute magnetic force using Maxwell stress tensor or energy method (F = ½ i² dL/dx or B²A/2μ₀)
- Part (c)(i): Define restriking voltage as transient voltage across breaker contacts post-current zero, RRRV as rate of rise of restriking voltage (kV/μs), and express V_restrike(max) = 2V_m and RRRV_max = ω₀V_m where ω₀ = 1/√(LC)
- Part (c)(ii): Identify SF6 circuit breaker as preferred for 132 kV and above due to superior dielectric strength and arc quenching capability
- Part (c)(iii): Calculate L = 5/314 = 15.92 mH, C = 0.03 μF, natural frequency f₀ = 1/(2π√(LC)), V_restrike(max) = 2√2 × 132/√3 kV, and RRRV_max = V_restrike(max) × ω₀
Q8 50M calculate Signal processing, control systems, state space analysis
(a) A signal is given by
x[t] = cos(28πt) + 2cos(40πt) + 3cos(70πt)
This signal is sampled at 90 samples/s to get discrete-time signal x(n).
(i) Find the periodicity of the individual components in the signal and hence find the periodicity N₀ of the signal x(n).
(ii) Find the harmonic indices m (0 ≤ m < N₀) of the complex DTFS coefficient Dₘ, where Dₘ is non-zero.
(iii) By inspection, write the magnitude of the coefficients |Dₘ| for the indices found above. 20 marks
(b) For a unity feedback time delay system with open-loop transfer function
G(s) = Ke⁻ᵀˢ/s(s+2)
calculate—
(i) the maximum tolerable value of delay T, when K = 1;
(ii) phase margin when K = √5 and delay T = 0·5 second. 20 marks
(c) Given a system in state space representation as
[ẋ₁] [0 1][x₁] [0]
[ẋ₂] = [0 -3][x₂] + [1] u
y = [1 0][x₁]
[x₂]
(i) Check whether the system is observable or not.
(ii) Find the state transition matrix.
(iii) Design a state feedback controller to place closed-loop poles at −1±2j. 20 marks
Answer approach & key points
Calculate all numerical results with systematic derivations, allocating approximately 35% time to part (a) on DTFS periodicity and harmonic analysis, 30% to part (b) on time-delay stability using Nyquist/Bode criteria, and 35% to part (c) on state-space design including observability test, matrix exponential computation, and pole placement via Ackermann's formula or direct method. Present each sub-part with clear headings, show all intermediate steps, and conclude with boxed final answers.
- For (a)(i): Compute digital frequencies ω₁=28π/90, ω₂=40π/90, ω₃=70π/90; find periods N₁=45, N₂=9, N₃=9; determine fundamental period N₀=LCM(45,9,9)=45
- For (a)(ii): Identify harmonic indices m₁=14, m₂=20, m₃=35 (or equivalently m₃=-10 mod 45 = 35) where Dₘ is non-zero within 0≤m<45
- For (a)(iii): State |D₁₄|=0.5, |D₂₀|=1, |D₃₅|=1.5 with correct conjugate symmetry |D₄₅₋ₘ|=|Dₘ|
- For (b)(i): Apply Nyquist stability criterion; find phase crossover frequency ωₚc=√2 rad/s; compute maximum delay Tₘₐₓ=π/(2√2)≈1.11s for K=1
- For (b)(ii): At K=√5, find gain crossover frequency ωgc=1 rad/s; calculate phase margin without delay as 90°-arctan(0.5)=63.43°; subtract delay phase ωgc×T×180/π=28.65° to get PM≈34.8°
- For (c)(i)-(iii): Check observability rank[O]=rank[C;CA]=2 (observable); compute state transition matrix Φ(t)=[1 (1-e⁻³ᵗ)/3; 0 e⁻³ᵗ]; design state feedback K=[5 3] using desired characteristic equation s²+2s+5=0