Electrical Engineering 2022 Paper II 50 marks Calculate

Paper II — Q6

(a) A three-phase, 50 Hz transmission line is 400 km long. The voltage at the sending end is 220 kV. The line parameters are r =…

(a)
(i)

A three-phase, 50 Hz transmission line is 400 km long. The voltage at the sending end is 220 kV. The line parameters are r = 0.125 Ω/km, x = 0.4 Ω/km and y = 2.8 × 10⁻⁶ mho/km. Find the sending-end current and receiving-end voltage when there is no load on the line. Comment on the result.

(ii)

Find the maximum permissible line length if the receiving-end no-load voltage is not to exceed 230 kV.

(iii)

Find the maximum permissible line frequency if the no-load voltage is not to exceed 250 kV. 20 marks

(b)
(i)

Two 11 kV, 25 MVA, three-phase, star-connected generators G₁ and G₂ operate in parallel. The positive, negative and zero sequence reactances of each generator are j0.09 pu, j0.05 pu and j0.04 pu respectively. A single line to ground fault occurs at the terminals of one of the generators. Find the fault current in pu. Also, find the voltage across the grounding resistor Rₙ in pu. Assume that the neutral of only generator G₁ is grounded through a resistor Rₙ = 1Ω. 10 marks

(ii)

A 50 Hz, 11 kV, three-phase synchronous generator with earthed neutral has a reactance of 4 Ω/phase and is connected to a busbar through a circuit breaker (CB). The capacitance to earth for the CB and generator is 0.02 μF per phase, and resistance may be ignored. Find the maximum voltage across the contacts of the circuit breaker, frequency of the transient oscillation and the average rate of rise of restriking voltage up to the first peak of the oscillation. 10 marks

(c)

Find the capacity of the cascade connection of n binary symmetric channels with the same crossover probability ε. What is the capacity when the number of channels goes to infinity? 10 marks

हिंदी में प्रश्न पढ़ें
(a)
(i)

एक त्रि-कला, 50 Hz संचरण लाइन 400 km लंबी है। इसके प्रेषण सिरों पर वोल्टता 220 kV है। संचरण लाइन के पैरामीटर r = 0.125 Ω/km, x = 0.4 Ω/km तथा y = 2.8 × 10⁻⁶ mho/km हैं। प्रेषण सिरों पर धारा एवं अभिग्राही सिरों पर वोल्टता ज्ञात कीजिए, जब संचरण लाइन पर कोई भार न हो। प्राप्त किए गए परिणामों पर टिप्पणी कीजिए।

(ii)

संचरण लाइन की अधिकतम अनुमेय लंबाई ज्ञात कीजिए, जिससे अभिग्राही सिरों पर शून्य-भार वोल्टता 230 kV से अधिक न हो।

(iii)

अधिकतम अनुमेय लाइन आवृत्ति ज्ञात कीजिए, जिससे शून्य-भार वोल्टता 250 kV से अधिक न हो। (20 अंक)

(b)
(i)

11 kV, 25 MVA के दो त्रि-कला, तारा-संयोजित जनर G₁ और G₂ समानांतर क्रम में प्रचालित हैं। प्रत्येक जनर के धनात्मक, ऋणात्मक एवं शून्य अनुक्रम प्रतिबाधा क्रमश: j0.09 pu, j0.05 pu तथा j0.04 pu हैं। एक जनर के सिरों पर एक लाइन से ग्राउंड दोष घटित होता है। दोष-धारा pu में एवं भूसंपर्क प्रतिरोध Rₙ के आर-पार वोल्टता pu में ज्ञात कीजिए। मान लीजिए कि केवल जनर G₁ का न्यूट्रल, Rₙ = 1Ω के प्रतिरोधक द्वारा भूसंपर्कित है। (10 अंक)

(ii)

50 Hz, 11 kV के भूसंपर्कित न्यूट्रल वाले एक त्रि-कला लुप्यकालिक जनर की प्रतिबाधा 4 Ω/कला (फेज) है तथा यह परिपथ-विघाटक द्वारा बसबार से जुड़ा हुआ है। परिपथ-विघाटक एवं जनर की भू के सापेक्ष संधारिता 0.02 μF प्रति फेज है। प्रतिरोध को उपेक्षित किया जा सकता है। परिपथ-विघाटक के संपर्क के आर-पार अधिकतम वोल्टता, अल्यकालिक दोलन की आवृत्ति तथा दोलन के प्रथम शिखर तक पुन:प्रवर्ती वोल्टता के बढ़ने की औसत दर ज्ञात कीजिए। (10 अंक)

(c)

n द्विंकी सममित चैनलों, जिनकी संक्रमण प्रायिकता समान रूप से ε है, के सोपानी संबंधन की क्षमता ज्ञात कीजिए। यदि चैनलों की संख्या अंशंख्य कर दी जाए, तो क्षमता क्या होगी? (10 अंक)

Q6 of the 2022 UPSC Mains Electrical Engineering Paper II, as printed
The question as printed in the 2022 Electrical Engineering paper

Model answer

Drafted with AI by UPSC Answer Check against this question's marking rubric, to the expected length. UPSC does not publish answers for Mains — this is one way to score well, not an official key. How we build rubrics and answers.

(a) The 400 km line at no load

Per km, z = 0.125 + j0.4 = 0.419∠72.6° Ω and y = j2.8 × 10⁻⁶ S. Then

γ = √(zy) = √(1.173 × 10⁻⁶ ∠162.6°) = 1.083 × 10⁻³ ∠81.3° = (1.634 × 10⁻⁴ + j1.071 × 10⁻³) per km, Zc = √(z/y) = √(1.497 × 10⁵ ∠−17.4°) = 386.9∠−8.7° Ω.

For l = 400 km, γl = 0.0654 + j0.4283. Using cosh(a + jb) = cosh a cos b + j sinh a sin b and sinh(a + jb) = sinh a cos b + j cosh a sin b,

cosh γl = 1.0021 × 0.9097 + j0.0654 × 0.4154 = 0.9116 + j0.0272 = 0.9120∠1.7°, sinh γl = 0.0654 × 0.9097 + j1.0021 × 0.4154 = 0.0595 + j0.4162 = 0.4205∠81.9°.

(i) With IR = 0 the long-line equations give VS = VR cosh γl and IS = (VR/Zc) sinh γl. Hence

VR = VS/cosh γl = 220/0.9120 = 241.2 kV (line-to-line), lagging VS by about 1.7°,

and, per phase, VR = 241.2/√3 = 139.3 kV, so

IS = 139.3 × 10³ × 0.4205/386.9 = 151 A, at an angle of 81.9° + 8.7° ≈ 90° ahead of VR.

Comment: at no load the receiving-end voltage is 9.6% higher than the sending-end voltage, and the sending-end current of 151 A is almost purely leading. This is the Ferranti effect: the line's charging current flows through its series inductance and the resulting voltage rise, roughly ω²LC l²/2 of VS, adds to the receiving-end voltage. It is why long EHV lines are fitted with shunt reactors that are switched in at light load.

(ii) Maximum length for VR ≤ 230 kV at no load. The condition is |cosh γl| ≥ 220/230 = 0.9565. To a good approximation cosh γl ≈ 1 + γ²l²/2 = 1 + zy l²/2 = (1 − 0.56 × 10⁻⁶ l²) + j0.175 × 10⁻⁶ l², and solving |cosh γl|² = 0.9149 gives l² ≈ 7.78 × 10⁴, l ≈ 279 km. Checking with the exact hyperbolic function at l = 280 km: γl = 0.0457 + j0.2998, cosh γl = 0.9564 + j0.0135, |cosh γl| = 0.9565 and VR = 220/0.9565 = 230.0 kV. The line may be at most about 280 km long.

(iii) Maximum frequency for VR ≤ 250 kV at 400 km. Both x and y are proportional to frequency while r is not. Let k = f/50; then z = 0.125 + j0.4k and y = j2.8 × 10⁻⁶ k, and the condition is |cosh γl| ≥ 220/250 = 0.88. With the same approximation, cosh γl ≈ (1 − 0.0896k²) + j0.028k, and |cosh γl|² = 0.7744 gives k ≈ 1.16. Checking exactly at k = 1.16 (58 Hz): γ = 1.249 × 10⁻³ ∠82.5° per km, γl = 0.0656 + j0.4954, cosh γl = 0.8817 + j0.0312, |cosh γl| = 0.8822 and VR = 249.4 kV; the limit is reached at about k = 1.17. The frequency may rise to about 58.5 Hz before the no-load voltage exceeds 250 kV. The steep dependence on frequency (a 17% rise in f gives a 3.6% rise in VR) is the reason the Ferranti rise is so sensitive to line length and system frequency.

(b)(i) Single line-to-ground fault at the generator terminals

Base 25 MVA, 11 kV, so Zbase = 11²/25 = 4.84 Ω and Rn = 1/4.84 = 0.2066 pu. The two identical generators are in parallel on the faulted bus, so the positive- and negative-sequence Thevenin reactances are halved: Z₁ = j0.09/2 = j0.045 pu, Z₂ = j0.05/2 = j0.025 pu. Only G₁'s neutral is grounded, so only G₁ provides a zero-sequence path, and the neutral resistor appears as 3Rn in the zero-sequence network: Z₀ = j0.04 + 3 × 0.2066 = 0.620 + j0.04 pu.

For a single line-to-ground fault the three sequence networks are in series with the prefault voltage E = 1.0 pu:

Ia1 = Ia2 = Ia0 = E/(Z₁ + Z₂ + Z₀) = 1/(0.620 + j0.110) = 1/(0.6295∠10.1°) = 1.589∠−10.1° pu.

Fault current If = 3Ia1 = 4.77∠−10.1° pu. With Ibase = 25 × 10⁶/(√3 × 11 × 10³) = 1312 A this is 6.25 kA.

All of the zero-sequence current, 3Ia0 = If, returns through G₁'s neutral, so the voltage across the grounding resistor is

VRn = If Rn = 4.77 × 0.2066 = 0.985 pu of phase voltage (0.985 × 6.35 = 6.25 kV).

The resistor limits the fault current to well under what a solid ground would give (with Rn = 0, If = 3/(0.11) = 27.3 pu) while leaving almost the full phase voltage across itself.

(b)(ii) Restriking voltage across the breaker

L = 4/(2π × 50) = 12.73 mH per phase, C = 0.02 μF, peak phase voltage Vm = √2 × 11,000/√3 = 8.98 kV.

Maximum restriking voltage (the peak of Vm(1 − cos ωn t)) = 2Vm = 17.96 kV ≈ 18 kV.

Frequency of the transient oscillation: fn = 1/(2π√(LC)) = 1/(2π√(12.73 × 10⁻³ × 0.02 × 10⁻⁶)) = 1/(2π × 1.596 × 10⁻⁵) = 9.97 kHz.

The first peak occurs at half a cycle of the oscillation, t = 1/(2fn) = 50.1 μs, so the average rate of rise of restriking voltage up to the first peak is 2Vm/(π√(LC)) = 17.96 kV/50.1 μs = 0.36 kV/μs (3.58 × 10⁸ V/s).

(c) Capacity of a cascade of binary symmetric channels

A single BSC with crossover probability ε has capacity C = 1 − H(ε), where H(ε) = −ε log₂ ε − (1 − ε) log₂(1 − ε). A cascade of n such channels is itself a BSC, since each stage flips the bit independently with probability ε and the output is in error when the bit has been flipped an odd number of times. Let εn be the overall crossover probability. Then ε₁ = ε and

εn = εn−1(1 − ε) + (1 − εn−1)ε, so that 1 − 2εn = (1 − 2ε)(1 − 2εn−1),

and by induction 1 − 2εn = (1 − 2ε)ⁿ, i.e.

εn = [1 − (1 − 2ε)ⁿ]/2.

The capacity of the cascade is therefore Cn = 1 − H(εn) = 1 − H([1 − (1 − 2ε)ⁿ]/2) bits per channel use.

As n → ∞, for any 0 < ε < 1, |1 − 2ε| < 1, so (1 − 2ε)ⁿ → 0 and εn → ½. Then H(εn) → 1 and Cn → 0: after enough noisy repeaters the output is independent of the input and no information gets through. Only for ε = 0 (a perfect channel, capacity 1 for all n) or ε = 1 (an inverter, also capacity 1) is the capacity preserved, which is the case for repeaters that regenerate the digital signal rather than merely pass it on.

How this answer will be evaluated

What earns full marks: Complete derivations with correct units and physical interpretation

Evaluation rubric

Each sub-part is marked on its own, against the marks and word limit printed on the paper.

  1. (a) Determine no-load line parameters and limits using long-line theory. 20 marks

    calculate— given → formula → substitution → result with units → interpretation

    Must cover

    • Calculate total line impedance Z and admittance Y
    • Apply hyperbolic functions for long-line model
    • No-load VR = 241.2 kV, IS ≈ 151 A leading, max length about 280 km for 230 kV
    • Max frequency about 58.5 Hz for 250 kV at 400 km

    Loses marks

    • Using short-line approximation for 400 km
    • Ignoring shunt admittance y

    Earns more

    • Comment on Ferranti effect
    • Show characteristic impedance Zc calculation

    Extra mark

    • Phasor diagram of sending/receiving end
  2. (b)(i) Find fault current and neutral voltage for parallel generators. 10 marks

    calculate— given → formula → substitution → result with units → interpretation

    Must cover

    • Construct sequence networks for parallel generators
    • Calculate zero-sequence impedance with grounding resistor
    • Determine fault current in per-unit
    • If ≈ 4.77 pu (6.25 kA), V across Rn ≈ 0.985 pu

    Loses marks

    • Ignoring ungrounded generator in zero-seq network
    • Incorrect per-unit base conversion

    Earns more

    • Correctly handle grounded vs ungrounded neutral
    • Show sequence network connection

    Extra mark

    • Phasor diagram of sequence currents
  3. (b)(ii) Analyze transient oscillation after circuit breaker opening. 10 marks

    calculate— given → formula → substitution → result with units → interpretation

    Must cover

    • Determine natural frequency of L-C circuit
    • 2Vm ≈ 18 kV, fn ≈ 9.97 kHz, average RRRV ≈ 0.36 kV/μs
    • Find average rate of rise of voltage
    • Use given capacitance and reactance values

    Loses marks

    • Ignoring capacitance to earth
    • Using wrong frequency formula

    Earns more

    • Show derivation of oscillation frequency
    • Calculate time to first peak

    Extra mark

    • Waveform sketch of transient voltage
  4. (c) Derive capacity of cascaded binary symmetric channels. 10 marks

    calculate— given → formula → substitution → result with units → interpretation

    Must cover

    • Define crossover probability for cascade
    • Derive capacity formula for n channels
    • Evaluate limit as n approaches infinity
    • Show entropy calculation

    Loses marks

    • Treating the cascade crossover probability as nε instead of [1 − (1 − 2ε)ⁿ]/2
    • Incorrect limit evaluation

    Earns more

    • Use binary entropy function H(p)
    • Show recursive probability relation

    Extra mark

    • Graph of capacity vs n
What "Calculate" is asking you to do

Apply the standard formula or schedule to data the question has already supplied — a table of readings, cost records, a balance sheet — and produce the number. The method is rarely in doubt; the marks sit in the named intermediate quantities, each of which has to appear as a labelled line.

Structure that answers it

Data as given → formula or standard treatment, named → substitution → each intermediate, labelled → result with units

Where marks are lost

Omitting an intermediate the marking scheme pays for separately, or rounding at an intermediate line so the final figure drifts. In commerce and accountancy, any figure in a statement that no numbered working note supports is treated as unearned.

All UPSC directive words, compared →

Practice this exact question

Write your answer and it is marked point by point against the model answer above — what you covered, what you missed, what you got wrong.

Evaluate my answer →

More from Electrical Engineering 2022 Paper II

Write this answer and get it marked in about 20 seconds

Free account: 5 AI evaluations a month, marked against the rubric above.

Start free

Already have an account? Log in