Electrical Engineering 2024 Paper II 50 marks Calculate

Paper II — Q6

(a) Calculate the power loss in the transmission system given in the following figure. The numerical values of transmission…

(a)

Calculate the power loss in the transmission system given in the following figure. The numerical values of transmission system are: I₁ = 0·75 ∠0° PU, I₂ = 0·8 ∠0° PU, V₃ = 1·2 ∠0° PU, Z₁ = (0·07 + j0·15) PU, Z₂ = (0·06 + j0·20) PU, Z₃ = (0·05 + j0·06) PU 20 marks

(b)

The fuel input equations of two power plant operations are given as: F₁ = 0·3 P₁² + 35 P₁ + 125, ₹/hr F₂ = 0·2 P₂² + 30 P₂ + 140, ₹/hr If the maximum and minimum loading on each unit is 90 MW and 20 MW respectively and the total consumption demand is 200 MW, then calculate the economical operating schedule and corresponding cost of generation. If load is equally shared by both units, calculate the savings achieved by loading the units as per equal incremental production cost. Neglect the transmission losses. 20 marks

(c)

A DM transmitter with a fixed step size of 0·25 V is given a sinusoidal message signal. Determine the maximum permissible amplitude of the message signal, if slope overload is to be avoided. Assume sampling frequency ten times the Nyquist rate. 10 marks

हिंदी में प्रश्न पढ़ें
(a)

निम्नलिखित चित्र में दी गई संचरण प्रणाली में शक्ति हानि की गणना कीजिए । संचरण प्रणाली के आंकिक मान निम्न प्रकार हैं : I₁ = 0·75 ∠0° PU, I₂ = 0·8 ∠0° PU, V₃ = 1·2 ∠0° PU, Z₁ = (0·07 + j0·15) PU, Z₂ = (0·06 + j0·20) PU, Z₃ = (0·05 + j0·06) PU 20 अंक

(b)

दो शक्ति संयंत्रों के संचालन के ईंधन निविष्ट समीकरण निम्न प्रकार हैं : F₁ = 0·3 P₁² + 35 P₁ + 125, ₹/घंटे F₂ = 0·2 P₂² + 30 P₂ + 140, ₹/घंटे यदि प्रत्येक इकाई पर अधिकतम व न्यूनतम भार क्रमशः: 90 MW और 20 MW तथा कुल खपत मांग 200 MW हो, तो मितव्ययी परिचालन अनुसूची और उससे संबंधित उत्पादन लागत की गणना कीजिए । यदि दोनों इकाइयों द्वारा कुल भार को समान रूप से सहभाजित किया जाता है, तो समान बढ़ोतरी उत्पादन लागत के अनुसार इकाइयों के भारण से प्राप्त बचत की गणना कीजिए । संचरण हानि को उपेक्षित किया गया है । 20 अंक

(c)

एक 0·25 V के स्थायी चरण परिमाण वाले DM प्रेषित्र (ट्रांसमीटर) को एक ज्यावक्रीय सूचना संकेत दिया जाता है । यदि प्रवणता अधिभार (स्लोप ओवरलोड) से बचना है, तो सूचना संकेत के अधिकतम अनुज्ञेय आयाम का निर्धारण कीजिए । न्यूनतम चयन आवृत्ति को नाइक्विस्ट दर से दस गुना माना गया है । 10 अंक

Q6 of the 2024 UPSC Mains Electrical Engineering Paper II, as printed
The question as printed in the 2024 Electrical Engineering paper

The figure this question refers to, in words

The question paper is a scan and the diagram did not survive as text. This is the figure as read from the original page — every component, value and label — so the question can be worked from the text below.

(a) A single-line diagram of a 4-bus power system: Bus 1 is connected to a generator G1 on the left and has bus voltage V1. Bus 2 is connected to a generator G2 on the right and has bus voltage V2. Transmission line L1 connects Bus 1 to Bus 3, carrying current I1 with an arrow directed from Bus 1 to Bus 3. Transmission line L2 connects Bus 2 to Bus 3, carrying current I2 with an arrow directed from Bus 2 to Bus 3. Bus 3 has bus voltage V3 and connects via line L3 to Bus 4, with line L3 carrying current I3 with an arrow directed towards Bus 4. Bus 4 connects to a load indicated by a leftward arrow labeled 'भार' (Load). The given system parameters are: I1 = 0.75 angle 0 degrees PU, I2 = 0.8 angle 0 degrees PU, V3 = 1.2 angle 0 degrees PU, line impedances Z1 = (0.07 + j0.15) PU, Z2 = (0.06 + j0.20) PU, and Z3 = (0.05 + j0.06) PU. The question asks to calculate the power loss in the transmission system.

(a) A power transmission system with 4 buses and 3 transmission lines: Bus 1 is connected to a generator G1 and has voltage V1. Transmission line L1 connects Bus 1 to Bus 3, carrying current I1 directed towards Bus 3. Bus 2 is connected to a generator G2 and has voltage V2. Transmission line L2 connects Bus 2 to Bus 3, carrying current I2 directed towards Bus 3. Bus 3 has voltage V3. Transmission line L3 connects Bus 3 to Bus 4, carrying current I3 directed towards Bus 4. Bus 4 connects to a load with current directed away from Bus 4 towards 'Load'.

Model answer

Drafted with AI by UPSC Answer Check against this question's marking rubric, to the expected length. UPSC does not publish answers for Mains — this is one way to score well, not an official key. How we build rubrics and answers.

(a) Power loss in the transmission system

Currents. At bus 3, I₁ and I₂ enter and I₃ leaves towards the load (KCL): I₃ = I₁ + I₂ = 0.75∠0° + 0.8∠0° = 1.55∠0° pu

Direct I²R loss. Line 1: 0.75² × 0.07 = 0.0394 pu Line 2: 0.80² × 0.06 = 0.0384 pu Line 3: 1.55² × 0.05 = 0.1201 pu P_L = 0.1979 pu The reactive loss is Q_L = 0.75² × 0.15 + 0.8² × 0.20 + 1.55² × 0.06 = 0.3565 pu.

Loss-formula (B-coefficient) method. V₃ is given so that the plant voltages and outputs, and hence the loss coefficients, can be found. V₁ = V₃ + I₁Z₁ = 1.2 + 0.75(0.07 + j0.15) = 1.2525 + j0.1125 = 1.2575∠5.13° pu V₂ = V₃ + I₂Z₂ = 1.2 + 0.8(0.06 + j0.20) = 1.248 + j0.160 = 1.2582∠7.31° pu P₁ = Re(V₁I₁*) = 0.9394 pu; P₂ = Re(V₂I₂*) = 0.9984 pu Plant 1's current flows through lines 1 and 3, and plant 2's through lines 2 and 3. Since both currents are at 0°, |V_i| cos φ_i = Re V_i: B₁₁ = (R₁ + R₃)/(|V₁| cos φ₁)² = 0.12/1.2525² = 0.0765 pu⁻¹ B₂₂ = (R₂ + R₃)/(|V₂| cos φ₂)² = 0.11/1.248² = 0.0706 pu⁻¹ B₁₂ = R₃/(|V₁| cos φ₁ |V₂| cos φ₂) = 0.05/(1.2525 × 1.248) = 0.0320 pu⁻¹ P_L = B₁₁P₁² + 2B₁₂P₁P₂ + B₂₂P₂² = 0.0675 + 0.0600 + 0.0704 = 0.1979 pu

Power-balance check. V₄ = V₃ − I₃Z₃ = 1.1225 − j0.093 pu, so P_load = Re(V₄I₃*) = 1.7399 pu. Then P₁ + P₂ − P_load = 1.9378 − 1.7399 = 0.1979 pu, which agrees. On a 100 MVA base the loss is 19.8 MW.

(b) Economic dispatch and saving over equal sharing

Incremental costs. dF₁/dP₁ = 0.6P₁ + 35 Rs/MWh; dF₂/dP₂ = 0.4P₂ + 30 Rs/MWh

Note on the printed limits. With an upper limit of 90 MW on each unit, the two units together can supply only 180 MW, so a 200 MW demand cannot be met at all. The question clearly intends the limits not to bind (for example, with an upper limit of 125 MW or more). The equal-λ schedule is therefore worked out below and checked against 20 MW ≤ P ≤ 125 MW.

Equal incremental cost. 0.6P₁ + 35 = 0.4P₂ + 30 with P₁ + P₂ = 200: 0.6P₁ + 35 = 0.4(200 − P₁) + 30 ⇒ P₁ = 75 MW P₁ = 75 MW, P₂ = 125 MW, λ = 80 Rs/MWh

Cost of the economic schedule. F₁ = 0.3(75)² + 35(75) + 125 = 4437.5 Rs/h F₂ = 0.2(125)² + 30(125) + 140 = 7015 Rs/h Total = 11 452.5 Rs/h

Equal sharing (100 MW each). F₁ = 0.3(100)² + 35(100) + 125 = 6625 Rs/h F₂ = 0.2(100)² + 30(100) + 140 = 5140 Rs/h Total = 11 765 Rs/h

Saving = 11 765 − 11 452.5 = 312.5 Rs/h (7500 Rs per day) Check by integration: moving 25 MW from unit 1 to unit 2 saves ∫ from 75 to 100 of (0.6P + 35) dP = 2187.5 Rs/h on unit 1 and costs ∫ from 100 to 125 of (0.4P + 30) dP = 1875 Rs/h on unit 2, a net saving of 312.5 Rs/h.

Diagram: Incremental fuel cost of the two units and the equal-λ dispatch for 200 MW

With equal sharing, unit 1 runs at 95 Rs/MWh and unit 2 at 70 Rs/MWh. Shifting load to the unit with the lower incremental cost reduces the total until the two incremental costs are equal.

(c) Maximum message amplitude in delta modulation

No slope overload. The staircase can rise by at most one step δ per sampling interval, so the message slope must not exceed δf_s: max |dm(t)/dt| ≤ δf_s

Sinusoidal message. For m(t) = A sin 2πf_mt, the maximum slope is 2πf_mA.

Sampling rate. Nyquist rate = 2f_m, so f_s = 10 × 2f_m = 20f_m.

Result. 2πf_mA ≤ δ × 20f_m ⇒ A ≤ 20δ/(2π) = 20 × 0.25/(2π) A_max = 2.5/π ≈ 0.796 V The limit is independent of the message frequency, because f_s is tied to f_m. A larger step would allow a larger amplitude but would increase granular noise when the signal changes slowly, which is the trade-off that adaptive delta modulation removes.

How this answer will be evaluated

What earns full marks: Correct method, clear steps, accurate calculations, and proper units.

Evaluation rubric

Each sub-part is marked on its own, against the marks and word limit printed on the paper.

  1. (a) Calculate the transmission loss for the given system (I₁ = 0.75, I₂ = 0.8, V₃ = 1.2 pu; Z₁, Z₂, Z₃ given). 20 marks

    calculate— given → formula → substitution → result with units → interpretation

    Must cover

    • KCL at bus 3: I₃ = I₁ + I₂ = 1.55 pu
    • Bus voltages V₁ = V₃ + I₁Z₁ = 1.2525 + j0.1125, V₂ = V₃ + I₂Z₂ = 1.248 + j0.16; plant outputs P₁ = 0.9394, P₂ = 0.9984 pu
    • Loss by I²R or B-coefficients: B₁₁ = (R₁ + R₃)/(|V₁| cos φ₁)² = 0.0765, B₂₂ = 0.0706, B₁₂ = 0.0320 ⇒ P_L = B₁₁P₁² + 2B₁₂P₁P₂ + B₂₂P₂²
    • P_L = 0.1979 pu (Q_L = 0.3565 pu)

    Loses marks

    • Using |I|²Z instead of |I|²R for real loss
    • Taking I₃ = I₁ − I₂

    Earns more

    • Power balance check: P₁ + P₂ − P_load(1.7399) = 0.1979
    • Loss expressed in MW for a stated base

    Extra mark

    • Explains why V₃ is needed (to get plant voltages and powers for the B-coefficient form)
  2. (b) Find the economic schedule and cost for 200 MW with F₁ = 0.3P₁² + 35P₁ + 125, F₂ = 0.2P₂² + 30P₂ + 140, limits 20–90 MW, and the saving over equal sharing. 20 marks

    calculate— given → formula → substitution → result with units → interpretation

    Must cover

    • Incremental costs 0.6P₁ + 35 and 0.4P₂ + 30; equal-λ with P₁ + P₂ = 200 ⇒ P₁ = 75 MW, P₂ = 125 MW, λ = 80 Rs/MWh
    • Points out that the printed 90 MW upper limit makes 200 MW infeasible (2 × 90 = 180 MW) and states the assumption used (limits not binding / upper limit ≥ 125 MW)
    • Cost: F₁ = 4437.5, F₂ = 7015, total 11 452.5 Rs/h
    • Equal sharing 100 + 100 MW: 6625 + 5140 = 11 765 Rs/h; saving 312.5 Rs/h

    Loses marks

    • Silently violating the stated limits without comment
    • Arithmetic errors in cost

    Earns more

    • Saving checked by integrating incremental costs
    • Annual/daily saving (7500 Rs/day)

    Extra mark

    • Incremental cost diagram
  3. (c) Find the maximum sinusoid amplitude for a DM with step 0.25 V, sampling at ten times the Nyquist rate, without slope overload. 10 marks

    calculate— given → formula → substitution → result with units → interpretation

    Must cover

    • Condition: max |dm/dt| ≤ δf_s
    • For A sin 2πf_m t, max slope = 2πf_mA
    • f_s = 10 × 2f_m = 20f_m
    • A_max = δf_s/(2πf_m) = 0.25 × 20/(2π) = 0.796 V, independent of f_m

    Loses marks

    • Using f_s = 10f_m
    • Omitting 2π

    Earns more

    • Explains slope overload and granular noise trade-off

    Extra mark

    • Adaptive DM mentioned
What "Calculate" is asking you to do

Apply the standard formula or schedule to data the question has already supplied — a table of readings, cost records, a balance sheet — and produce the number. The method is rarely in doubt; the marks sit in the named intermediate quantities, each of which has to appear as a labelled line.

Structure that answers it

Data as given → formula or standard treatment, named → substitution → each intermediate, labelled → result with units

Where marks are lost

Omitting an intermediate the marking scheme pays for separately, or rounding at an intermediate line so the final figure drifts. In commerce and accountancy, any figure in a statement that no numbered working note supports is treated as unearned.

All UPSC directive words, compared →

Practice this exact question

Write your answer and it is marked point by point against the model answer above — what you covered, what you missed, what you got wrong.

Evaluate my answer →

More from Electrical Engineering 2024 Paper II

Write this answer and get it marked in about 20 seconds

Free account: 5 AI evaluations a month, marked against the rubric above.

Start free

Already have an account? Log in