Electrical Engineering 2025 Paper II 50 marks Calculate

Paper II — Q7

(a) Two generators are connected in parallel to the low-voltage side of a 3-phase, Δ-Y transformer as shown below : Generator 1…

(a)

Two generators are connected in parallel to the low-voltage side of a 3-phase, Δ-Y transformer as shown below : Generator 1 is rated 60 MVA, 13·8 kV Generator 2 is rated 30 MVA, 13·8 kV

Each generator has a subtransient reactance of 20%. The transformer is rated 90 MVA, 13·8 Δ/69 Y kV with a reactance of 10%. Before the fault occurs, the voltage on the high-tension side of the transformer is 66 kV. The transformer is unloaded, and there is no circulating current between the generators. Find the subtransient current in each generator, when a 3-phase short circuit occurs on the high-tension side of the transformer : 20 marks

(b)
(i)

What is line coding? For the data sequence 10101110, draw the waveforms for the following line coding schemes : 1. Polar NRZ scheme 2. Bipolar NRZ scheme 3. Differential Manchester scheme 4. RZ polar scheme 10 marks

(ii)

A PCM system uses 4096 quantization levels to handle telephone signals with a volume range of 40 dB. 1. What is the SNR for maximum sinusoidal signal level? 2. What is the SNR level for the smallest sinusoidal signal level? 3. With a 10 dB compression provided, what will be the new SNR? 10 marks

(c)

With the help of schematic and circuit diagrams, describe the operation of a static differential protection relay, using the rectifier bridge amplitude comparator. 10 marks

हिंदी में प्रश्न पढ़ें
(a)

जैसा कि निम्न चित्र में दर्शाया गया है, दो जनित्र, एक 3-कला, Δ-Y परिणामित्र की निम्न-वोल्टता की ओर समानांतर में जुड़े हैं : जनित्र 1 की अनुमत क्षमता (रेटिंग) 60 MVA, 13·8 kV है जनित्र 2 की अनुमत क्षमता 30 MVA, 13·8 kV है

प्रत्येक जनित्र का उपक्षणिक प्रतिघात 20% है। परिणामित्र की अनुमत क्षमता (रेटिंग) 90 MVA, 13·8 Δ/69 Y kV, 10% प्रतिघात के साथ है। दोष (फॉल्ट) के पहले उच्च-वोल्टता की ओर परिणामित्र की वोल्टता 66 kV है। परिणामित्र पर कोई भार नहीं है, और जनित्रों के मध्य कोई भी परिसंचरण धारा नहीं है। प्रत्येक जनित्र की उपक्षणिक धारा का मान ज्ञात कीजिये, जबकि एक 3-कला लघु परिपथन (शॉर्ट सर्किट) दोष, परिणामित्र की उच्च-वोल्टता की ओर घटित होता है : (20 अंक)

(b)
(i)

लाइन कोडिंग क्या है? डाटा अनुक्रम 10101110 के लिये निम्नलिखित लाइन कोडिंग योजनाओं के तहत तरंगरूपों (वेवफॉर्म) को आरेखित कीजिये : 1. ध्रुवीय NRZ योजना 2. द्वि-ध्रुवीय NRZ योजना 3. विभेदक (डिफरेंशियल) मैनचेस्टर योजना 4. RZ ध्रुवीय योजना (10 अंक)

(ii)

एक PCM तंत्र 4096 कांटन स्तरों (क्वांटाइजेशन लेवल) का प्रयोग करते हुए 40 dB आयतन परास (वॉल्यूम रेंज) के टेलीफोन संकेतों को संभालता है। 1. उच्चतम ज्यावक्रीय संकेत स्तर के लिये SNR क्या है? 2. निम्नतम ज्यावक्रीय संकेत स्तर के लिये SNR स्तर क्या है? 3. 10 dB का संपीडन (कंप्रेशन) देने के साथ नया SNR क्या होगा? (10 अंक)

(c)

योजनाबद्ध एवं परिपथ आरेखों की सहायता से दिष्कारी (रेक्टिफायर) सेतु आयाम तुलनित्र (कंपरेटर) का प्रयोग करते हुए एक स्थिर (स्टैटिक) विभेदीय संरक्षण रिले की क्रियाविधि का वर्णन कीजिये। (10 अंक)

Q7 of the 2025 UPSC Mains Electrical Engineering Paper II, as printed
The question as printed in the 2025 Electrical Engineering paper

The figure this question refers to, in words

The question paper is a scan and the diagram did not survive as text. This is the figure as read from the original page — every component, value and label — so the question can be worked from the text below.

(a) Two generators G1 and G2 are connected in parallel to the primary (delta) side of a three-phase delta-star transformer. The secondary (star) side of the transformer is connected to a fault point F through a line, with a short-circuit fault indicated at F. The transformer is rated 90 MVA, 13.8 delta / 69 Y kV with a reactance of 10%. Generator 1 is rated 60 MVA, 13.8 kV and Generator 2 is rated 30 MVA, 13.8 kV, each with a subtransient reactance of 20%. The question asks to find the subtransient current in each generator when a 3-phase short circuit occurs on the high-tension side of the transformer.

(c) Graph of force F in newtons versus time t in seconds. The vertical axis is labelled F(N) with a marked value 0.2. The horizontal axis is labelled t with a marked value 4x10^-3 s. The waveform is a rectangular pulse: F = 0 for t < 0, F = 0.2 N constant from t = 0 to t = 4x10^-3 s, and F = 0 for t > 4x10^-3 s.

Model answer

Drafted with AI by UPSC Answer Check against this question's marking rubric, to the expected length. UPSC does not publish answers for Mains — this is one way to score well, not an official key. How we build rubrics and answers.

(a)

Choose common base S_base = 90 MVA (transformer rating). Base voltages: LV side 13.8 kV, HV side 69 kV. Base current on LV side: I_base(LV) = S_base / (√3 × V_base(LV)) = 90×10⁶ / (√3 × 13.8×10³) = 3765.33 A.

Generator subtransient reactances on their own bases are both 0.20 pu. Convert to 90 MVA base: X₁ = 0.20 × (90/60) = 0.30 pu. X₂ = 0.20 × (90/30) = 0.60 pu. Transformer reactance Xₜ = 0.10 pu on 90 MVA, 13.8/69 kV.

Pre-fault HV voltage = 66 kV. Since the transformer is unloaded, no voltage drop occurs, so the internal EMF behind each generator subtransient reactance equals this voltage. In per-unit on the 69 kV HV base: V₀ = 66/69 = 22/23 = 0.95652 pu. This is also the per-unit voltage on the LV side because the voltage bases are chosen in the transformer turns ratio.

The two generator subtransient reactances are in parallel, in series with the transformer reactance to the fault. Parallel generator reactance: X_p = (0.30 × 0.60) / (0.30 + 0.60) = 0.18 / 0.90 = 0.20 pu. Total reactance to fault: X_total = X_p + Xₜ = 0.20 + 0.10 = 0.30 pu.

Total subtransient fault current in per-unit: I_f = V₀ / X_total = (22/23) / 0.30 = (22/23) × (10/3) = 220/69 = 3.1884 pu.

The current divides between the parallel generators inversely as their reactances. The voltage across the parallel combination is the same, so: I₁ X₁ = I₂ X₂ ⇒ I₁/I₂ = X₂/X₁ = 0.60/0.30 = 2. Thus I₁ = (2/3) I_f and I₂ = (1/3) I_f.

I₁ = (2/3) × (220/69) = 440/207 = 2.1256 pu. I₂ = (1/3) × (220/69) = 220/207 = 1.0628 pu.

Actual RMS subtransient currents on the LV side: I₁(actual) = 2.1256 × 3765.33 = 8003.6 A. I₂(actual) = 1.0628 × 3765.33 = 4001.8 A.

(b)(i)

Line coding is the process of converting a binary data stream into a discrete-level (digital) voltage or current waveform for baseband transmission. It defines the levels, transitions, DC balance, and clock recovery properties.

Let bit duration be T_b, and use levels +V, −V, 0, with L and H as low and high levels. The data sequence is 1 0 1 0 1 1 1 0.

  1. Polar NRZ: 1 = +V, 0 = −V, held for the entire bit. Waveform levels: +V, −V, +V, −V, +V, +V, +V, −V.
  1. Bipolar NRZ (AMI): 1 alternates in polarity, 0 = 0 V. First 1 is positive. Ones occur at positions 1, 3, 5, 6, 7. Waveform levels: +V, 0, −V, 0, +V, −V, +V, 0.
  1. Differential Manchester: A mid-bit transition always occurs. A start transition represents 0, and no start transition represents 1. Assume the initial level before bit 1 is L. Half-bit pairs for bits 1 to 8: Bit 1 (1): L H Bit 2 (0): L H Bit 3 (1): H L Bit 4 (0): H L Bit 5 (1): L H Bit 6 (1): H L Bit 7 (1): L H Bit 8 (0): L H So the sequence is LH, LH, HL, HL, LH, HL, LH, LH. (The inverted waveform with initial H is equally valid.)
  1. RZ polar: 1 = positive for first half and zero for second half; 0 = negative for first half and zero for second half. Half-bit pairs: (+V,0), (−V,0), (+V,0), (−V,0), (+V,0), (+V,0), (+V,0), (−V,0).
Diagram: Line codes for 10101110: polar NRZ, bipolar NRZ (AMI), differential Manchester and polar RZ

(b)(ii)

Number of quantization levels M = 4096. Number of bits per sample: n = log₂ 4096 = 12 bits.

For a full-scale sinusoidal signal in uniform PCM, the maximum signal-to-quantization-noise ratio is: (S/N)_max = 1.76 + 6.02 n dB = 1.76 + 6.02 × 12 = 1.76 + 72.24 = 74.0 dB.

Volume range = 40 dB. The smallest sinusoidal signal is 40 dB below the maximum. Therefore: (S/N)_min = 74.0 − 40 = 34.0 dB.

With 10 dB compression, the effective dynamic range at the quantizer is reduced by 10 dB, i.e., from 40 dB to 30 dB. Hence the new minimum SNR is: (S/N)_min(new) = 74.0 − 30 = 44.0 dB. The maximum SNR stays at about 74.0 dB in this idealised model; in practice the companding penalty lowers it slightly.

(c)

Static differential protection relay using a rectifier bridge amplitude comparator:

Schematic: current transformers CT₁ and CT₂ are placed on the two sides of the protected equipment (transformer, generator or busbar) and connected in the Merz-Price circulating-current arrangement. Two quantities are derived from the CT secondaries:

  • Operating (differential) quantity: the spill current I_d = I₁ − I₂ (phasor difference), taken from the equipotential points of the pilot loop through an auxiliary transformer.
  • Restraining (bias) quantity: the through current I_r = (I₁ + I₂)/2, taken through a centre-tapped bias transformer in the pilot loop.

Circuit: each quantity is fed to its own full-wave rectifier bridge. Bridge BR_op gives a DC voltage V_op ∝ |I_d| and bridge BR_r gives V_r ∝ k|I_r|, where k is the percentage-bias setting. The two bridge outputs are connected in opposition (circulating-current comparator) across a static level detector (transistor or op-amp comparator) that fires a thyristor to energise the trip coil. Capacitors smooth the rectified outputs, and a setting resistor fixes the minimum pick-up.

Normal load or external (through) fault: I₁ ≈ I₂ and in phase, so I_d ≈ 0 (only CT mismatch error) while I_r is large. V_r > V_op, the net comparator input has restraining polarity, and the relay does not operate.

Internal fault: both sides feed the fault, so the phasor difference I_d becomes large (with infeed from both ends it approaches the total fault current) and exceeds k|I_r|. V_op > V_r, the level detector switches, the thyristor fires, the trip coil is energised and the circuit breaker opens.

Because the magnitudes compared are those of the phasor difference and the phasor sum, phase information is retained; comparing |I₁| with |I₂| alone would fail for an internal fault fed equally from both ends. The percentage-bias characteristic (|I_d| > k|I_r| plus a small minimum setting) keeps the relay stable on heavy through faults with CT saturation or tap mismatch, yet sensitive to internal faults. Being static, the relay has no moving parts, low CT burden, fast operation (about one cycle) and high reliability.

Diagram: Static biased differential relay: spill current I1 - I2 feeds the operating bridge, through current feeds the restraint bridge via a centre-

How this answer will be evaluated

Framework: null

What earns full marks: Complete, accurate, and well-structured answers with all required elements and correct calculations.

Evaluation rubric

Each sub-part is marked on its own, against the marks and word limit printed on the paper.

  1. (a) Subtransient current in each generator during a 3-phase fault on the HT side. 20 marks

    calculate— given → formula → substitution → result with units → interpretation

    Must cover

    • Base 90 MVA; base current LV 3765.33 A; V0 = 66/69 = 0.95652 pu
    • X1 = 0.30, X2 = 0.60, Xt = 0.10 pu; Xp = 0.20; Xtotal = 0.30 pu
    • If = 220/69 = 3.1884 pu; division I1:I2 = X2:X1 = 2:1 → I1 = 2.1256 pu, I2 = 1.0628 pu
    • Actual currents 8003.6 A and 4001.8 A (LV side)

    Loses marks

    • Using different bases without conversion
    • Incorrect parallel reactance calculation
    • Missing units in final answer

    Earns more

    • Correct per-unit conversion for each component
    • Accurate calculation of parallel reactance
    • Proper application of current division rule
    • Final answer in both per-unit and amperes

    Extra mark

    • Phasor diagram showing current distribution
    • Verification of total current equals sum of individual currents
  2. (b)(i) Definition of line coding and waveforms for four specified schemes. 10 marks

    describe— define → structure or process in order → labelled diagram → significance

    Must cover

    • Line coding defined
    • Polar NRZ levels and waveform (+V,−V,+V,−V,+V,+V,+V,−V)
    • Bipolar NRZ (AMI): +V,0,−V,0,+V,−V,+V,0 with alternating ones; waveform drawn
    • Differential Manchester (LH,LH,HL,HL,LH,HL,LH,LH) and RZ polar half-bit pairs; both waveforms drawn (figure provided)

    Loses marks

    • Missing or incorrect waveform for any scheme
    • No definition of line coding
    • Confusing transition rules for Differential Manchester

    Earns more

    • Accurate timing and amplitude for each scheme
    • Clear labeling of bits and transitions
    • Proper representation of RZ polar scheme
    • Consistent time scale across all waveforms

    Extra mark

    • Comparison table of scheme characteristics
    • Note on DC component or bandwidth for each
  3. (b)(ii) SNR values for maximum, minimum, and compressed signal levels. 10 marks

    calculate— given → formula → substitution → result with units → interpretation

    Must cover

    • n = log₂4096 = 12 bits; (S/N)max = 1.76 + 6.02n = 74.0 dB
    • (S/N)min = 74 − 40 = 34.0 dB
    • 10 dB compression → effective dynamic range 30 dB → new min SNR 44.0 dB
    • Maximum SNR ≈74.0 dB (ideal model; companding penalty lowers it slightly in practice)

    Loses marks

    • Incorrect quantization level calculation
    • Missing compression effect on SNR
    • No units or dB notation in final answers

    Earns more

    • Correct use of 4096 quantization levels
    • Proper application of volume range (40 dB)
    • Accurate compression calculation
    • Clear step-by-step derivation

    Extra mark

    • Formula for quantization noise power
    • Note on dynamic range improvement
  4. (c) Operation of static differential protection relay with rectifier bridge comparator. 10 marks

    describe— define → structure or process in order → labelled diagram → significance

    Must cover

    • Schematic: CT₁, CT₂ on both sides in Merz-Price loop; operate bridge fed by spill current I₁−I₂, restraint bridge fed by through (bias) current (I₁+I₂)/2
    • V_op ∝ |I₁−I₂| opposed to V_r ∝ k|I₁+I₂|/2 at a static level detector → thyristor → trip coil (percentage-bias characteristic)
    • Normal/external fault: I₁ ≈ I₂ → no operation; internal fault: differential current → trip
    • Static-relay features: no moving contacts, fast response, low burden

    Loses marks

    • Missing schematic or circuit diagram
    • No explanation of comparator operation
    • Comparing |I₁| with |I₂| only (loses phase; fails for equal infeed internal fault) or confusing differential with directional protection

    Earns more

    • Clear labeling of components in diagram
    • Explanation of normal vs fault conditions
    • Role of setting resistor or bias
    • Response to through-faults vs internal faults

    Extra mark

    • Circuit diagram with component values
    • Note on sensitivity or pickup current
What "Calculate" is asking you to do

Apply the standard formula or schedule to data the question has already supplied — a table of readings, cost records, a balance sheet — and produce the number. The method is rarely in doubt; the marks sit in the named intermediate quantities, each of which has to appear as a labelled line.

Structure that answers it

Data as given → formula or standard treatment, named → substitution → each intermediate, labelled → result with units

Where marks are lost

Omitting an intermediate the marking scheme pays for separately, or rounding at an intermediate line so the final figure drifts. In commerce and accountancy, any figure in a statement that no numbered working note supports is treated as unearned.

All UPSC directive words, compared →

Practice this exact question

Write your answer and it is marked point by point against the model answer above — what you covered, what you missed, what you got wrong.

Evaluate my answer →

More from Electrical Engineering 2025 Paper II

Write this answer and get it marked in about 20 seconds

Free account: 5 AI evaluations a month, marked against the rubric above.

Start free

Already have an account? Log in